U.S. Installations (see note 1) 
Canadian Installations (see note 2)
A = 
Clearance above grade, veranda, porch,  
12 inches (30 cm) 
12 inches (30 cm) 
 
deck, or balcony
B = 
Clearance to window or door that may be   4 feet (1.2 m) below or to side of opening;  
36 inches (91 cm) 
 
opened 
1 foot (30 cm) above opening
C = 
Clearance to permanently closed window 
See note 4 
See note 5
D = 
Vertical clearance to ventilated soffit located 
 
above the terminal within a horizontal  
See note 4 
See note 5 
 
distance of 2 feet (61cm) from the center  
 
line of the terminal
E = 
Clearance to unventilated soffit 
See note 4 
See note 5
F =  Clearance to outside corner 
See note 4 
See note 5
G =  Clearance to inside corner 
See note 4 
See note 5
H = 
Clearance to each side of center line 
 
3 feet (91 cm) within a height 15 feet above 
 
extended above meter/regulator assembly  See note 4 
the meter/regulator assembly
I = 
Clearance to service regulator vent outlet 
See note 4 
3 feet (91 cm)
J =  Clearance to nonmechanical air supply inlet 
 
to building or the combustion air inlet to 
4 feet (1.2 m) below or to side of opening; 
36 inches (91 cm) 
 
any other appliance 
1 foot (30 cm) above opening
K = 
Clearance to a mechanical air supply inlet  3 feet (91 cm) above if within 10 feet (3 m) 
6 feet (1.83 m) 
  
horizontally
  
 
Vent termination not allowed in this location 
  
Vent termination not allowed in this location  for category IV appliances.  A vent shall not 
L = 
Clearance above paved sidewalk or paved  for category IV appliances.  For Category III  terminate directly above a sidewalk or paved 
 
driveway located on public property 
appliances, vent must terminate at least 7 
driveway that is located between two single 
 
 
feet (2.13m) above the sidewalk or driveway.  family dwellings and serves both dwellings. 
 
 
 
For Category III appliances that do not violate 
 
 
 
the previous condition, vent must terminate 
 
 
 
at least 7 feet (2.13m) above the sidewalk or 
 
 
 
driveway.
M = 
Clearance under veranda, porch, deck,  
See note 4 
12 inches (30 cm) (see note 3) 
 
or balcony
Notes:
1.  In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code.
2.  In accordance with the current CSA-B149.1 Installation Codes.
3.  Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
4.  For clearances not specified in ANSI Z223.1 / NFPA 54, clearance is in accordance with local installation codes and the requirements of  
  the gas supplier.
5.  For clearances not specified in CSA-B149.1, clearance is in accordance with local installation codes and the requirements of the gas supplier.
Figure 3. Combustion Air and Vent Through Side Wall.