Bradford-White Corp Water Heater BWCH Manual De Usuario

Descargar
Página de 64
Page 8
 
B
RADFORD
 W
HITE
 C
ORP.
Figure 2. Combustion Air and Vent Through Roof.
 
 
EACH OPENING*
 
SIZE 
SQUARE INCHES 
SQUARE CM
 500 
125 
807
 750 
188 
1213
 1000 
250 
1613
 1250 
313 
2020
 1500 
375 
2420
 1750 
438 
2826
 2000 
500 
3226
*Net Free Area in Square Inches / Square cm
Area indicated is for one of two openings; one at floor level and 
one at the ceiling, so the total net free area could be double the 
figures indicated.
This chart is for use when communicating directly with the 
outdoors. For special conditions and alternate methods, refer to 
the latest edition of ANSI Z223.1.
Note:
  Check with louver manufacturers for net free area of 
louvers. Correct for screen resistance to the net free area 
if a screen is installed. Check all local codes applicable to 
combustion air.
Table 3. Combustion Air Openings.
SECTION 2. 
Venting and Combustion Air
2.1  Combustion Air
Copper Brute II boilers and water heaters must 
have provisions for combustion and ventilation air 
in accordance with Section 5.3, Air for Combustion 
and Ventilation, of the National Fuel Gas Code, ANSI 
Z223.1, or Sections 7.2, 7.3 or 7.4 of CSA B149.1, 
Installation Codes, or applicable provisions of the local 
building codes.
A Copper Brute II appliance may receive 
combustion air from the space in which it is installed, 
or it can be ducted directly to the unit from the outside. 
Ventilation air must be provided in either case.
2.1.1  Combustion Air From Room
In the United States, the most common 
requirements specify that the space shall communicate 
with the outdoors in accordance with method 1 or 2, 
which follow. Where ducts are used, they shall be of 
the same cross-sectional area as the free area of the 
openings to which they connect.
Method 1: Two permanent openings, one 
commencing within 12 inches (30 cm) of the top 
and one commencing within 12 inches (30 cm) of 
the bottom, of the enclosure shall be provided. The 
openings shall communicate directly, or by ducts, 
with the outdoors or spaces that freely communicate 
with the outdoors. When directly communicating 
with the outdoors, or when communicating to the 
outdoors through vertical ducts, each opening shall 
have a minimum free area of 1 square inch per 4000 
Btu/hr (5.5 square cm/kW) of total input rating of all 
equipment in the enclosure. When communicating to 
the outdoors through horizontal ducts, each opening 
shall have a minimum free area of not less than 
1 square inch per 2000 Btu/hr (11 square cm/kW) of 
total input rating of all equipment in the enclosure. 
Table 3
 shows data for this sizing method, for each 
Copper Brute II model.
Method 2: One permanent opening, commencing 
within 12 inches (30 cm) of the top of the enclosure, 
shall be permitted. The opening shall directly 
communicate with the outdoors or shall communicate 
through a vertical or horizontal duct to the outdoors 
or spaces that directly communicate with the outdoors 
and shall have a minimum free area of 1 square inch 
per 3000 Btu/hr (7 square cm/kW) of the total input 
rating of all equipment located in the enclosure. This 
opening must not be less than the sum of the areas of 
all vent connectors in the confined space.
Other methods of introducing combustion and 
ventilation air are acceptable, providing they conform 
to the requirements in the applicable codes listed 
above.
In Canada, consult local building and safety 
codes or, in absence of such requirements, follow CSA 
B149.1.
2.1.2  Intake Combustion Air
The combustion air can be taken through the 
wall, or through the roof. When taken from the wall, 
it must be taken from out-of-doors by means of the 
Bradford White horizontal wall terminal (see 
Table 2
). 
When taken from the roof, a field-supplied rain cap or 
an elbow arrangement must be used to prevent entry of 
rain water (
see Figure 2
).
Use single-wall galvanized pipe, per 
Table 4
, for 
the combustion air intake (see 
Table 2
 for appropriate 
size). Route the intake to the heater as directly as 
possible. Seal all joints with tape. Provide adequate 
hangers. The unit must not support the weight of the 
combustion air intake pipe. Maximum linear pipe