Bradford-White Corp Water Heater BWCH Manual De Usuario

Descargar
Página de 64
Page 40
 
B
RADFORD
 W
HITE
 C
ORP.
Programming. 
Mode 2 is used in primary-secondary 
piping hydronic systems without outdoor reset. Mode 
5 adds outdoor reset.
Step 1: Install the additional sensor in the 
primary loop (see 
Figure 4
), and wired to the “SC2” 
and “SUPS” terminals on the field wiring panel 
(Figure 23).
Step 2: 
Remove the factory-installed jumper 
between the “HtD” and “ComD” terminals on the 
field wiring panel (
Figure 14
), and connect a zone 
valve or pump end switch or other contact closure 
device (aquastat, etc.) to these terminals to provide an 
indication of heat demand in the system. 
Note: The boiler must have an indication of heat 
demand to fire. If a zone valve or pump end switch is 
not connected to the “HtD” and “ComD” terminals, the 
jumper must be left in place. However, the boiler pump 
(if equipped) and any pump connected to a contactor 
wired to the PMP-PMP terminals on the field wiring 
panel will run continuously and not cycle off according 
to the setting for the Pump Delay. In addition, the LCD 
screen will always show “dem” (demand) and will not 
allow cycling of the display to verify all the sensor 
settings.
Step 3: 
Press the three programming buttons 
to enter 
ADJUST mode (
Figure 25
). Press Item to 
select the programming item, and the 
ARROW
 keys 
to adjust the setting. See 
Section 6.3 Programming 
the Temperature Control
 if more programming 
instructions are needed.
Recommended settings for hydronic system with 
180°F / 83°C primary loop temperature:
Item F° 
MODE 
2
BOIL TARGET 
180 
83
BOIL MASS 
1
DIFF 20 
10
DLY 
5:00 
5:00
F° 
F° 
°C
Step 4: 
See 
Section 6.4.11 Limit Controls.
 Set 
both high limit controls at least 25°F / 14°C higher 
than the 
BOIL TARGET to allow for temperature rise 
across the heat exchanger.
6.3.4  Choosing the Mode for your 
Application
This section describes various applications and 
the recommended field wiring and Mode selections.
Mode 1:
  Boiler operates using its own inlet 
and outlet sensors only, not relying 
on a remote thermostat, aquastat, 
or external sensor.
This setup is most commonly found in domestic 
hot water applications with a continuous run pump. 
This is not recommended for other applications.
The Copper Brute II is shipped with a jumper 
between the “Com D” and “Ht D” terminals, which 
must remain in place to allow the unit to fire. The unit 
will fire whenever the outlet temperature cools below 
the target temperature.
Important Note: If the Copper Brute II is pump-
mounted at the factory, or if a field-supplied pump 
contractor is connected to the Copper Brute II’s pump 
contactors 
(Pmp Pmp), the user must program the controller’s 
pump delay (DLY) setting to ON. When ON is selected, 
pump operation is continuous. The unit’s inlet and 
outlet sensors must be able to detect the temperature 
in the storage tank in order to control it. Without the 
tank water continuously running through the heater, 
the heater will have no way of knowing what the 
temperature in the tank is, and will not be able to 
respond to a change in tank temperature. Short cycling 
or lack of hot water may result if the pump does not 
run continuously.
Mechanical aquastat in a domestic hot 
water storage tank.
Remove the jumper from the “Com D” and 
“HtD” terminals and connect the aquastat’s leads to 
these terminals. This connection uses a standard, non-
powered mechanical aquastat. When the aquastat calls 
for heat, the Copper Brute II’s temperature control will 
respond and start the boiler pump (if equipped) and 
fire the boiler.
If the Copper Brute II is not a pump mounted 
model, a 24VAC pump contactor may be connected to 
the “PMP” terminals to control a field installed pump. 
(If desired, the pump can run continuously, with the 
aquastat telling the heater when to fire.)
Program the temperature control to use Mode 1. 
The 
AUTO/MAN
 switch must be in the 
AUTO
 position in 
this mode.
Mode 3:  Bradford White R2014800 sensor 
installed in the domestic hot water 
storage tank.
The Copper Brute II ships with a jumper between 
the “Com D” and “Ht D” terminals. Verify this jumper 
is in place, and connect the sensor leads to the “S C2” 
and “SUP S” terminals. When the sensor detects a 
temperature below the target temperature, the control 
will respond and start the heater pump (if equipped) 
and fire the heater. 
If the heater is not a pump mounted model, a 
24VAC pump contactor may be connected to the 
“PMP” terminals to control a field installed pump. (If 
desired, the pump can run continuously).
Program the temperature control to use Mode 3. 
The 
AUTO/MAN
 switch must be in the 
AUTO
 position in 
this mode.