B4 Volume Water Heater
Page 15
SECTION 3.
Operation
3.1  Controls - General
See Figure 15 for control locations.
        3.1.1        Electronic Ignition Controls:
         a.     Intermittent Ignition:
                 Pilots are automatically lit when the 
operating aquastat calls for heat (System 
#9).
                 The unit performs its own safety check and 
opens the main valves only after the pilot is 
proven to be lit. Whenever the pilot flame 
is interrupted, the main gas valve closes 
within 0.8 seconds.
         b.     Electronically Supervised Standing Pilot 
System (System #16):
                 When pilot flame fails, the ignition control 
module responds in less than 0.8 seconds 
and provides 100% safety shutdown.
        3.1.2 
Operating Controls:
         Electrically Operating Controls:
         Copper Brute units are equipped with operating 
temperature. The temperature sensing bulb is 
located in the heater inlet.
        
3.1.3 
High Limit Controls:
         The manual reset high limit switches are 
provided as standard equipment on all heaters. 
Automatic reset switches are optionally provided. 
The temperature sensing bulb of the switch is 
always located in the heater outlet. Burners will 
automatically shut down whenever overheating 
of water occurs.
        3.1.4 
Flow Switch:
         Standard on all models, the switch is mounted 
directly in the header outlet. The flow switch 
shuts down all burners in case of low water 
condition or pump failure.
        3.1.5 
Low Water Cut Off: (Optional)
         The low water cut off automatically shuts off  the 
heater whenever the water level drops below the 
probe. The probe is located at the heater inlet.
3.2  Initial Start-Up
Before placing the heater in operation, be certain 
that the heater is filled with water and all air is purged 
from the system. Once the heater is connected to the 
gas supply, the automatic safety shutoff devices must 
be checked.
1.      Before beginning the tests, make sure the main 
manual gas valve, and any other heater firing 
valves are in the “OFF” position.
Rating Plate
Ignition Control
Pressure Relief
Valve
Flow Switch
In
Out
Transformer
Terminal Strip
Operating Control
(Aquastat)
Hi-Limit
Operating
Gas Valve
Manual
Pilot
Valve
Manual
Main Gas
Valve
Safety
Gas
Valve
Figure 15. Control Components.