Bradford-White Corp 500-1825 Manual De Usuario

Descargar
Página de 20
Internet Version for Reference Only
 
BRADFORD WHITE
Page 16
B4 Volume Water Heater
Page 17
When a tank aquastat is not used:
The pump on the heater must run continuously, 
so the heater's temperature control will sense the tank's 
water temperature. Set the heater temperature control 
to the desired tank temperature. Set the manual reset 
high limit 50°F higher than the heater temperature 
control. Example: If desired temperature is 140°F, set 
the heater temperature control at 140°F, and set the 
manual reset high limit at 190°F.
3.4  To Turn Off Heater:
1.      Turn off main electric switch.
2.      Close all manual gas valves.
3.5  To Shut Down System:
To shut down heater, turn off all manual gas 
valves and electrical disconnect switches. Whenever 
danger of freezing exists, shut off water supply and 
remove drain plug in the bottom of front header 
cover. Drain every part of system subject to freezing 
temperature.
SECTION 4.
Maintenance
1.      Lubricate the water circulating pump (see 
instructions found on the pump).
2.      If a strainer is employed in a pressure reducing 
valve or in piping, clean it every six (6) months.
3.      At start-up and every six (6) months thereafter, 
the pilot and main burner flame should be 
observed for proper performance (see Figure 18). 
See attached lighting and shut-down instructions 
for proper pilot flame pattern). If flame has the 
appearance of “sooting” tips, check for debris 
near orifices. Call serviceman.
4.      Inspect the venting system for obstruction, 
leakage and corrosion at least once each year.
5.      Keep heater area clear and free from combustible 
material, gasoline and other flammable 
vapors and liquids (see Table 1 for minimum 
clearances).
6.      Be certain all combustion air and ventilation 
openings are unobstructed.
7.      Check for fouling on the external surfaces of 
the heat exchanger every six months. (NOTE: 
After installation and first start-up, check the heat 
exchanger for fouling after the following periods 
of operation: 24 hours, 7 days, 30 days, 90 days, 
and once every six months thereafter).
         Fouling on the external surfaces of the heat  
exchanger is caused by incomplete combustion 
and is a sign of combustion air and/or venting 
problems. As soon as any fouling is observed, 
the cause of the fouling should be corrected (see 
Section 5, Troubleshooting Guide). The heat 
exchanger can be checked by locating a mirror 
under the burners with a flashlight. An alternate 
method is to remove the venting and top panel as 
necessary to inspect from above. Also check the 
vent system for defects at this time.
         a.     If cleaning is required, shut off all electrical  
and gas supply to the heater.
         b.     To expose the heat exchanger:
       Indoor Models:
         Remove flue pipe, top of unit, rear upper jacket, 
flue collector rear panel and heat exchanger 
baffles.
       Outdoor Models:
         Remove vent top assembly, rear upper jacket, 
flue collector rear panel and heat exchanger 
baffles.
         c.     Remove all burners:
        It is usually more convenient to remove 
the  burner tray assembly. Disconnect 
sensor wire, ignition cable (or thermocouple 
generator) and pilot gas line. Disconnect 
manifold inlet union(s). Remove the four 
(4) retaining screws. Grasp burner/pilot 
assembly firmly at the front. Push it back, 
disengaging it from the gas orifice. Lower 
the front of the burner (to avoid damaging 
pilot shield) then remove the burner tray.
Pilot Reset
Switch
Figure 17. Pilot Safety Relay.
Figure 18. Main Burner Flame Pattern.