Beckett CG10 Manual De Usuario

Descargar
Página de 32
5
CG10 Burner Manual
Figure 1. Burner Nameplate
Pre-installation Checklist 
If there is risk of the space being under negative 
pressure, or of exhaust fans or other devices depleting 
available air for combustion and ventilation, the 
appliance/burner should be installed in an isolated room 
provided with outside combustion air.
Indoor Installation
Combustion air supply
General Model Information
Serial Number, 
Including Date Code
Rating Information
Approval Agency 
Symbols
Primary Group 
and Fuel
R.W. Beckett
Construction and Setting Data
R.W. Beckett Specifi cation
Number and Revision
Boiler Manufacturer and Model,
When Applicable
Additional Codes
Section: Pre-installation Checklist
Adequate Combustion and 
Ventilation Air Supply 
 
 
      Required
Failure to provide adequate air supply could 
seriously affect the burner performance and result in 
damage to the equipment and emission of poisonous 
carbon monoxide gas.
 
The burner cannot properly burn the fuel if it is not 
supplied with a reliable combustion air source. 
Follow the guidelines in the latest edition of National 
Fuel Gas Code ANSI Z223.1 (NFPA 54) and 
CAN1-B149.1 regarding providing adequate air for 
combustion and ventilation. 
For appliance/burner units in confi ned spaces, the 
room must have an air opening near the top of the 
room, plus one near the fl oor, each with a free area 
at least one square inch per 1000 Btu/hr input for all 
fuel-burning equipment in the room.
y
y
y
Protect against Dust and 
Moisture
Wet or dusty environments could lead to blocked 
air passages, corrosion damage to components, 
impaired combustion performance and result in 
asphyxiation, explosion or fi re.
This burner is designed for clean, dry installations.
Electrical controls are not protected against rain or 
sprayed liquids.
Keep the installation clear of dust, dirt, corrosive 
vapors, and moisture.
Protective covers and more frequent maintenance 
may be required.
y
y
y
y