Flange mounting arrangement (Includes high-
temperature gasket and /or fi ber rope for pressure 
fi ring).
Verify fi ring input range
Refer to appliance manufacturer’s instructions (if 
available) for the fi ring input range. Otherwise the 
maximum recommended fi ring range for the burner 
depends on the length and width of the fi ring chamber 
and the distance from the burner center to the chamber 
fl oor. Verify that the chamber dimensions are at least as 
large as the minimum values given in Figure 2. If the 
appliance dimensions are smaller, reduce the fi ring rate 
accordingly. 
Minimum Combustion
Chamber Dimensions (inches)
Input 
Firing 
Rate in 
MBH
Length 
‘L’
Width 
‘W’
Height 
‘H’
Burner Head 
Centerline to 
fl oor ‘A’
300-400
18
12
12
6
400-600
22
14
14
7
600-900
26
16
16
8
900-1200
30
18
18
9
Figure 2. Minimum Combustion Chamber Dimensions
Clearances
With the burner installed in the appliance, there must 
be adequate space in front of and on the sides of the 
burner to allow access and operation.  Verify that the 
clearance dimensions comply with local codes and with 
the appliance manufacturer’s recommendations.
Fuel gas supply
Verify that the gas supply piping complies with all 
applicable local codes and the latest edition of the 
National Fuel Gas Code ANSI Z223.1 (NFPA 54).  
Insure that the supply gas pipe size is capable of 
providing at least the minimum pressure required to the 
burner gas train inlet at the burner’s full capacity rating. 
Refer to Table 1.
Flue vent system
The fl ue gas vent system must be in good condition 
and must comply with National Fuel Gas Code ANSI 
Z223.1 (NFPA 54) and all other applicable codes having 
jurisdiction for vent construction, capacity, and sizing.
Electrical supply
Check the nameplate on the burner to verify that the 
power connections available are correct for the burner. 
Refer to Figure 1. All power must be supplied through 
fused disconnect switches and comply with the latest 
edition of National Electric Code NFPA 70 (Canada CSA 
C22.1) and all other local or applicable codes. 
Verify burner components
Burner model can be checked from burner carton or 
rating label on burner.
Test For Gas Pipe Leaks
Leaking gas could result in asphyxiation, explosion, 
or fi re hazard.
The gas supply piping must be absolutely leak-free. 
Pressure test the gas piping with air that is at least 
three times greater than the gas pressure being 
used.
Verify that there are no leaks before proceeding.
y
y
y
Section: Pre-installation Checklist
Dimensions shown are for cast 
iron sectional boilers with uptakes 
between sections. For minimum dimensions of other 
furnace types consult R.W. Beckett Corporation.