Burnham Series 8H/8HE Boiler Instruccion De Instalación

Descargar
Página de 84
28
V. Gas Piping
Failure to properly pipe gas supply to boiler may 
result in improper operation and damage to the 
boiler or structure.  Always assure gas piping is 
absolutely leak free and of the proper size and 
type for the connected load.
An additional gas pressure regulator may be 
needed.  Consult gas supplier.
A.
  Size gas Piping. Design system to provide adequate gas 
supply to boiler. Consider these factors:
1.  Allowable pressure drop from point of delivery to 
boiler. Maximum allowable system pressure is ½ 
psig.  Actual point of delivery pressure may be less; 
contact gas supplier for additional information. 
Minimum allowable gas valve inlet pressure is 
indicated on rating label.
2.  Maximum gas demand. Table 5 lists boiler input 
rate. Also consider existing and expected future gas 
utilization equipment (i.e. water heater, cooking 
equipment).
3.  Length of piping and number of fittings. Refer to 
Table 6 for maximum capacity of Schedule 40 pipe. 
Table 7 lists equivalent length for standard fittings.
Boiler 
Model
Rated Capacity
(cubic feet per hour)
Gas
Connection 
Size
Natural
LP / Propane
805H
252
100.8
1
806H
315
126.0
1
807HE
340
136.0
1
808HE
410
164.0
1
809HE
460
184.0
1
810HE
505
202.0
1
Table 5:  Rated Input
4.  Specific gravity of gas. Gas piping systems for 
gas with a specific gravity of 0.70 or less can be 
sized directly from Table 6, unless authority having 
jurisdiction specifies a gravity factor be applied. 
For specific gravity greater than 0.70, apply gravity 
factor from Table 8. If exact specific gravity is not 
shown choose next higher value.
  For materials or conditions other than those listed 
above, refer to the National Fuel Gas Code
NFPA 54/ANSI Z223.1 and/or CAN/CSA B149.1 
Installation Codes, or size system using standard 
engineering methods acceptable to authority having 
jurisdiction.
Failure to use proper thread compounds on all 
gas connectors may result in leaks of flammable 
gas.
Gas supply to boiler and system must be 
absolutely shut off prior to installing or servicing 
boiler gas piping.
B.
  Connect boiler gas valve to gas supply system.
1.  Use methods and materials in accordance with local 
plumbing codes and requirements of gas supplier. In 
absence of such requirements, follow the National 
Fuel Gas Code, NFPA 54/ANSI Z223.1 and/or 
CAN/CSA B149.1 Installation Codes.
2.  Use thread (joint) compound (pipe dope) resistant to 
action of liquefied petroleum gas.
3.  Install sediment trap, ground-joint union and manual 
shut-off valve upstream of boiler gas valve and 
outside jacket. See Figure 22.
4.  All above ground gas piping upstream from 
manual gas valve must be electrically continuous 
and bonded to a grounding electrode. Do not use 
gas piping as a grounding electrode. Refer to the 
National Electrical Code, ANSI/NFPA 70 and/or 
CSA C22.1 Electrical Code.
USA boilers built for installation at altitudes greater than 2,000 feet above sea level have been specially 
orificed to reduce gas input rate 4 percent per 1,000 feet above sea level per the National Fuel Gas Code, 
NFPA  54/ANSI  Z223.1,  Section  8.1.2  and Appendix  F.    Canadian  boilers’  orifice  sizing  is  indicated  on  the 
rating label.  High altitude boiler models are identifiable by the model number’s tenth digit on the rating label. 
(4=2000’ - 4500’, 5= 2000’ - 5000’)