Burnham Series 8H/8HE Boiler Manual De Propietario
16
Inspect existing chimney before installing boilers.
failure to clean or replace perforated pipe or tile
lining will cause severe injury or death.
2.1 Vents, or breeching ducts, are generally less flexible
in design location than are water pipes, gas pipes
or electrical lines. To avoid conflicts for a given
location, design and layout the vents in this section
before proceeding to other sections of this manual.
2.2 Obtain a scaled drawing of the boiler room. Note the
floor size, ceiling height, exterior walls, and chimney
location, if provided.
2.3 Determine the input required to the system. It is
recommended that the heating load be determined by
an accurate calculation of the heat loss of the structure
using methods contained in the ASHRAE Guide. If
service water is to be added capacity as described in
paragraph 3.13 of this manual. The boiler capacity
so obtained is net rating to input. Record the input
required on the boiler room drawing.
2.4 Using Figure 2-2 for the input found in 2.3 above, find
the number of modules recommended. Those module
combinations shown represent the best selection for
lowest first cost. Other combinations may be selected,
within the following guidelines:
1) Modules using a sequencing control system, such
as Tekmar described in Section 5.0, should not
vary by more than one size.
2) Modules using a combined vent system should not
vary by more than one size.
3) The combined vent sizing procedures in this
section are based on a maximum of eight modules
using a common vent system. If it is desired to
serve more than eight modules with a common
vent system, the specific requirements should
be referred to the BURNHAM COMMERCIAL
Application Engineering Department.
Refer to Figure 2-3 for individual module inputs.
2.4.1 Sketch on the boiler room drawing the approximate
location of the modules. Figures 2-4 thru 2-9 show
several layouts that can be used depending on the size
and shape of the boiler room and chimney location,
if provided. Refer to Figure 2-3 for dimensional data
on individual modules. Select the layout which best
fits the boiler room. Bear in mind that for combined
vent systems it is desirable to keep horizontal laterals
as short as possible. On a combined vent system for
which a fixed chimney is provided, it is desirable to
place the first module close to the chimney.
2.4.2 If the factory fabricated water manifolds are to be
used, 805H, 806H, and 807HE modules should be laid
out with 28½” module spacing and 808HE, 809HE,
and 810HE modules should be laid out with 40”
module spacing. If an 807HE and an 808HE module
are to be connected to a common manifold, use the
longer manifold with 40” spacing. Otherwise, any
module spacing that allows at least 1 inch jacket –to-
jacket spacing if acceptable, pending local or state
code requirements that may require greater module to
module spacing.
2.4.3 Refer to Figure 2-10 for minimum clearances around
modules to combustible materials and for service
access. CAUTION: Local fire ordinances may be
more restrictive and should be complied with.
2.5 One of the serious errors made in layout of a boiler
room is the failure to provide sufficient ventilation
air. Insufficient ventilation air will cause incomplete
combustion, poor ignition, accumulation of soot in
the boiler, or the production of toxic gases. Many
service calls for dirty boilers, nuisance lock outs,
noisy ignition, or obnoxious odors are traceable to
insufficient ventilation air. Use Figure 2-11 at the
input desired to find the recommended free area of the
ventilation opening required. Reference to Figures
1-2 thru 1-4 should be made in order to understand
the types of installations described in the headings
of Figure 2-11. Record the free ventilation area
required on the plans of the boiler room and sketch
the openings like those shown in figures 1-2 thru 1-4
respectively.
2.6 Individual vents as shown in Figure 1-7 are highly
recommended if the job site conditions allow.
Individual vents are particularly useful in boiler rooms
having a low ceiling height. Individual vents are
easy to design and in many cases result in the lowest
installed cost. They also are the most dependable in
operation and less susceptible to condensation than are
combined vents. To size individual vents, use Figure
2-12 with the vent height available, the lateral length,
size of module and type of vent pipe.
2.7 Combined vents will perform satisfactorily if strict
design procedures are followed. Referring to Figures
2-4 thru 2-9, note that a connector rise F of at least
one foot is required. A connector rise F of three feet
is desirable. Thus, to make the desired connector rise
and have space for the manifold vent, the minimum
boiler room ceiling height must be equal to:
32½” Module Height
+ )
Drafthood Height
+ F
Minimum Connector Rise
+ CV Manifold Diameter
+ 6”
Clearance
=
Minimum Ceiling Height
If the minimum ceiling height above is not available,
common vents will not perform satisfactorily and
should not be used.
sEcTION 2.0 VENTs