Burnham Series 8H/8HE Boiler Manual De Propietario

Descargar
Página de 72
16
Inspect existing chimney before installing boilers.  
failure to clean or replace perforated pipe or tile 
lining will cause severe injury or death.
2.1    Vents, or breeching ducts, are generally less flexible 
in design location than are water pipes, gas pipes 
or electrical lines.  To avoid conflicts for a given 
location, design and layout the vents in this section 
before proceeding to other sections of this manual.
2.2    Obtain a scaled drawing of the boiler room.  Note the 
floor size, ceiling height, exterior walls, and chimney 
location, if provided.
2.3    Determine the input required to the system.  It is 
recommended that the heating load be determined by 
an accurate calculation of the heat loss of the structure 
using methods contained in the ASHRAE Guide.  If 
service water is to be added capacity as described in 
paragraph 3.13 of this manual.  The boiler capacity 
so obtained is net rating to input.  Record the input 
required on the boiler room drawing.
2.4    Using Figure 2-2 for the input found in 2.3 above, find 
the number of modules recommended.  Those module 
combinations shown represent the best selection for 
lowest first cost.  Other combinations may be selected, 
within the following guidelines:
1)   Modules using a sequencing control system, such 
as Tekmar described in Section 5.0, should not 
vary by more than one size.
2)   Modules using a combined vent system should not 
vary by more than one size.
3)   The combined vent sizing procedures in this 
section are based on a maximum of eight modules 
using a common vent system.  If it is desired to 
serve more than eight modules with a common 
vent system, the specific requirements should 
be referred to the BURNHAM COMMERCIAL 
Application Engineering Department.
Refer to Figure 2-3 for individual module inputs.
2.4.1  Sketch on the boiler room drawing the approximate 
location of the modules.  Figures 2-4 thru 2-9 show 
several layouts that can be used depending on the size 
and shape of the boiler room and chimney location, 
if provided.  Refer to Figure 2-3 for dimensional data 
on individual modules.  Select the layout which best 
fits the boiler room.  Bear in mind that for combined 
vent systems it is desirable to keep horizontal laterals 
as short as possible.  On a combined vent system for 
which a fixed chimney is provided, it is desirable to 
place the first module close to the chimney.
2.4.2  If the factory fabricated water manifolds are to be 
used, 805H, 806H, and 807HE modules should be laid 
out with 28½” module spacing and 808HE, 809HE, 
and 810HE modules should be laid out with 40” 
module spacing.  If an 807HE and an 808HE module 
are to be connected to a common manifold, use the 
longer manifold with 40” spacing.  Otherwise, any 
module spacing that allows at least 1 inch jacket –to-
jacket spacing if acceptable, pending local or state 
code requirements that may require greater module to 
module spacing.
2.4.3 Refer to Figure 2-10 for minimum clearances around 
modules to combustible materials and for service 
access.  CAUTION:  Local fire ordinances may be 
more restrictive and should be complied with.
2.5    One of the serious errors made in layout of a boiler 
room is the failure to provide sufficient ventilation 
air.  Insufficient ventilation air will cause incomplete 
combustion, poor ignition, accumulation of soot in 
the boiler, or the production of toxic gases.  Many 
service calls for dirty boilers, nuisance lock outs, 
noisy ignition, or obnoxious odors are traceable to 
insufficient ventilation air.  Use Figure 2-11 at the 
input desired to find the recommended free area of the 
ventilation opening required.  Reference to Figures 
1-2 thru 1-4 should be made in order to understand 
the types of installations described in the headings 
of Figure 2-11.  Record the free ventilation area 
required on the plans of the boiler room and sketch 
the openings like those shown in figures 1-2 thru 1-4 
respectively.
2.6    Individual vents as shown in Figure 1-7 are highly 
recommended if the job site conditions allow.  
Individual vents are particularly useful in boiler rooms 
having a low ceiling height.  Individual vents are 
easy to design and in many cases result in the lowest 
installed cost.  They also are the most dependable in 
operation and less susceptible to condensation than are 
combined vents.  To size individual vents, use Figure 
2-12 with the vent height available, the lateral length, 
size of module and type of vent pipe.
2.7    Combined vents will perform satisfactorily if strict 
design procedures are followed.  Referring to Figures 
2-4 thru 2-9, note that a connector rise F of at least 
one foot is required.  A connector rise F of three feet 
is desirable.  Thus, to make the desired connector rise 
and have space for the manifold vent, the minimum 
boiler room ceiling height must be equal to:
 
  32½”  Module Height
 
  +   ) 
Drafthood Height
 
  +  F 
Minimum Connector Rise
 
  +  CV  Manifold Diameter
  
+  6” 
Clearance
 
  =  
Minimum Ceiling Height
 
  If the minimum ceiling height above is not available, 
common vents will not perform satisfactorily and 
should not be used.
sEcTION 2.0 VENTs