Burnham Series 8H/8HE Boiler Manual De Propietario

Descargar
Página de 72
18
7)   If a tapered or graduated manifold vent is desired, 
such as in Figure 1-6 the horizontal and vertical 
portion of the vent serving five modules is also 
complete with 6) above.  However, to size the 
manifold vent at an intermediate position such as 
CV3 in Figure 2-4, use Figure 2-13 for the MBH 
Input of the modules served by that position of the 
manifold vent.  The Input MBH of each module 
can be determined from Figure 2-3.  In this case 
CV3 serves two modules having an input of 
920 MBH.  Enter figure 2-13 at an input of 920 
MBH.  Move right to H = 10 Ft. and find CV3 
= 14” diameter.  Mark this vent diameter size on 
the drawing of the boiler room.  Thus a graduated 
manifold vent design is complete.  It is possible 
with this procedure to reduce the manifold vent 
size after each module.  However, from a practical 
standpoint, the cost of fittings may offset the lower 
cost of smaller vent pipe.
2.10    All of the above procedure is based on data found 
in the ASHRAE Guide, 1975 Equipment Volume, 
Chapter 26.  The basic chimney equation is expressed 
as follows:
RELATIONshIP Of INPUT, GROss OUTPUT, AND 
NET RATING fOR sERIEs 8h/8hE MODULEs
fIGURE 2-1
where:  I = Operating heat input, BTUH
 
    di = Inside diameter of the common vent or    
         manifold vent
 
M =   Mass flow input ratio, lb. of products per            
1000 BTU of fuel burned.  A value of 1.60 was  
   used based on 5.3% CO
2
 after dilution.  An    
   additional 15% dilution was added for each    
   unfired module.
 
∆P =   Pressure difference or loss in the system              
acting to cause flow, inches of water.  Use  
        
     0.537 inches water per 100 Ft. of pipe.
B  =    Sea level barometer used —29.92” Hg
K   =   Resistance loss coefficients, dimensionless.
Tm =  Temperature in vent system at average  
 
     conditions, °Fabs.
  The serious Engineer should become familiar with the 
above basic equation and the range of the variables that 
may be encountered.  The tables in Figures 2-12 thru 
2-14 should not be extrapolated.  If system conditions 
do not fall within the limit of the tables, vent sizes must 
be calculated using the chimney equation above as 
described in the ASHRAE Guide.
               (di)² 
(∆PB) 
0.5
I = 4.13 x 10
5  
x   M       x    (KTm)