Burnham Series 8H/8HE Boiler Manual De Propietario
20
fIGURE 2-3
boiler
Model
Input
(Mbh)
Dimensions (inch)
Recommended
chimney size
(Round)
water
content
(Gallons)
Approx.
shipping
weight (Lb)
"A'
"b"
"c"
"D"
"E"
805H
252
20
10
7
24-13/16
16-1/8
7" dia. x 15 ft.
11.9
680
806H
315
23-3/4
11-7/8
8
27-13/16
18
8" dia. x 15 ft.
13.9
770
807HE
340
27-1/2
13-3/4
9
27-13/16
18
8" dia. x 15 ft
.
15.9
870
808HE
410
31-1/4
15-5/8
9
30-13/16
20
8" dia. x 15 ft
17.9
950
809HE
460
35
17-1/2
10
33-1/2
22
10" dia. x 15 ft
19.9
1040
810HE
505
38-3/4
19-3/8
10
33-1/2
22
10" dia. x 15 ft
21.9
1140
(1) Special base required for installations on combustible flooring; adds 4-3/4" to boiler height (floor to jacket top panel is 37-1/4").
(2) Gas connection size: 1 NPT
(3) Maximum Allowable Working Pressure: 50 psi (Water Only)
(4) Items shown in hidden lines supplied by installer.
(2) Gas connection size: 1 NPT
(3) Maximum Allowable Working Pressure: 50 psi (Water Only)
(4) Items shown in hidden lines supplied by installer.