Burnham Series 4N Boiler Instruccion De Instalación

Descargar
Página de 24
17
See item 10 under Operating Instruction if it becomes 
necessary to add water to the boiler more frequently 
than once a month.
 
1.   GENERAL
 
Inspection should be conducted annually. Service 
as frequently as specified in paragraphs below. Before 
service or maintenance is performed complete boiler 
shutdown/cooldown procedure.
2.   BOILER SHUT DOWN AND COOLDOWN    
 
 PROCEDURE
NOTE:
 This procedure is generally required in 
preparation for   corrective or preventative maintenance 
in the unit. This procedure must be supervised by an 
individual who is thoroughly qualified in operation and 
maintenance of the equipment at hand. This is written 
with Steam Boilers in mind, but the principles are 
applicable to Hot Water Boilers as well.
A.  Decrease plant load as much as possible.
B.  Turn boiler switch off. If control power from  
burner is used to support accessories, leave on 
until boiler system has cooled down.
C.  Shut and lock manual gas and oil valves as  
applicable.
D.  In single boiler installations, some small steam  
loads can remain on to assist in a controlled  
cooldown of the boiler (i.e., deaerator). In multiple  
boiler installations, shut down the non-return 
valve and the back up valve. Lock them shut.
E. Allow the boiler feed pump to remain active. As 
the boiler cools down, the water level is reduced 
by demand or shrinkage. It is best to be aware of 
the boiler level at all times.
F.  When boiler pressure has decreased to 5 to 
10 psi on the pressure gauge, open the boiler 
manual vent valve on the top of the boiler. This 
is to act as a sentinel against the increase in 
pressure and to prevent the boiler from going into 
a vacuum. Lock the valve open.
NOTE: Depending on the size of the boiler, the large 
mass of heating surfaces that are still hot can cause the 
boiler water temperature to increase, even if the gauge 
pressure is “0”. It is better to allow the entire system to 
cool gradually, never force cool the boiler as damage 
can also be inflicted due to “thermal shock.”
G.  When boiler and water are below 120°F, shut off    
power to the unit and lock out the circuit    
 
breakers. 
H.  If required, open front and rear doors for   
 
observation of fireside surfaces. 
I.  Drain boiler down as far as required. (Usually  
completely.) Make sure the vent valve on the top 
of the boiler remains open. Open and lock the 
float control low water cutoff drain valves. These 
will serve as additional vents.
J.  Shut and lock the boiler feed valves, and any  
 
blowdown valves that can be affected by other  
boilers in the same facility (i.e., bottom blow down 
valves can tie into a common blowdown 
separator in a multiple boiler installation).
K.  If necessary to remove handhole and/or manhole  
plates for water side inspection or maintenance,  
use extreme caution. Loosen the nuts securing 
the arch enough to allow the plate to drop  
approximately 1/8 inch when tapped loose with    
a mallet. Once again, ensure the pressure in the    
boiler is “0” before loosening the plate. Remove  
the plate the remainder of the way. Wear gloves    
and eye protection at all times. 
3.   CLEAN THE BOILER HEATING SURFACES  
 
AND FLUE   
 
At least once each year, preferably at the end of the 
heating season.
A.  Clean the vent System
Vent system should be checked annually for:
1. Obstructions.
2.  Accumulations of soot.
3.  Deterioration of vent pipe or vent accessories   
due to condensation or other reasons. 
4.  Proper support  no sags, particularly in 
horizontal runs.
5.  Tightness of joints.
 
Remove all accumulations of soot with a wire 
brush and vacuum. Remove all obstructions. Replace 
deteriorated parts and support properly. Seal all joints.
B.  Clean the Boiler Heating Surfaces
   At the end of the heating season, clean boiler  
 
heating surfaces thoroughly. Access to boiler  
firetubes may be gained by removing the front 
and rear smokeboxes or smokebox doors.  
 
Where applicable, remove the turbulators, paying  
close attention to which tubes have turbulators.  
SECTION Iv  — SERvICE INSTRUCTIONS