Burnham Series 4N Boiler Instruccion De Instalación
19
9. ATTENTION TO THE BOILER WHILE NOT IN
OPERATION.
If a boiler is not used during the winter months, and
it is in a place subject to freezing, it must be fully
drained to prevent freezing damage.
A. Steam Boilers Procedure for taking steam
boilers off line at the end of heating season: Drain
off boiler water until it runs clear while holding the
boiler temperature between 180 and 200ºF. Then
refill to top of gauge glass.
B. Water Boilers Since a water boiler is a closed
system, no draining/refilling should be necessary.
C. Note any time raw water is introduced into the
boiler it must be immediately heated to 180°F to
drive off dissolved gases. If water treatment is
used, sufficient water treatment compound should
be added to condition the make-up water.
10. REPAIR PARTS
Give boilers series and model number when
ordering repair parts. All repair parts can be ordered
through your local representative or call us at 888-791-
3790.