To change the call for heat source that the 
circulator is activated from (see Figures 8 - 13 
for examples), press the 
“▲”
 and 
“▼”
 keys until 
the following screen is displayed:


Press 
“ENTER (RESET)
 to toggle the circulator 
source between ON TTON ZR, and ON BOTH.
Press 
CANCEL (BACK)”
 to exit.
D. Changing Domestic Hot Water Priority 
(DHWP) Setting
The Domestic Hot Water Priority function temporarily 
overrides the HeatManager Dynamic Temperature Reset 
functionality when there is a call for domestic hot water. 
This ensures that hot water will be produced when 
needed.  It also temporarily turns off either the C1 or ZC 
outputs (depending on the DHWP and circulator source 
settings) to give priority to the DHWP zone when it calls 
for heat.  See Figures 8-13 for examples of how to use 
these settings for maximum benefi t.
In any mode other than an OPTION sub-menu, press 
the 
“OPTION
 key.  The following screen appears:


Press the 
“▲”
 and 
“▼”
 keys until the following 
screen is displayed:


Press 
“ENTER (RESET)
.  The following screen 
will be displayed:


Press the 
“▲”
 and 
“▼”
 keys until the following 
screen is displayed:


Press 
“ENTER (RESET)
 to toggle between OFF, 
ON TT, and ON ZR settings.  See wiring diagrams in 
Figures 11 thru 13 for proper wiring with DHWP on.
Press 
CANCEL (BACK)”
 to exit.
c.
4.
1.
2.
3.
4.
5.
6.
E. Selecting Fahrenheit or Celsius 
Temperature Display
In any mode other than an OPTION sub-menu, press 
the 
“OPTION
 key.  The following screen appears:


Press the 
“▲”
 and 
“▼”
 keys until the following 
screen is displayed:


Press 
“ENTER (RESET)
.
  The following screen 
will be displayed:


Press the 
“▲”
 and 
“▼”
 keys until the following 
screen is displayed:
()

Press 
“ENTER (RESET)”
 to toggle between °F and °C.
Press 
CANCEL (BACK)”
 to exit.
F. Changing Low Water Cut-Off (LWCO) 
Setting
The Low Water Cut-off function is active when the 2-in-1 
sensor is used with the AquaSmart control to prevent the 
burner from fi ring without suffi cient water present in the 
boiler.  The DELAY OFF time can be selected to delay 
the response of the control to a low-water condition.  The 
DELAY ON time can be selected to delay the response 
of the control when the boiler water returns to a suffi cient 
level.  The RESET function can be set to AUTO or MAN 
(manual) to control how the AquaSmart will return from a 
LOCKOUT LOW WATER condition when the boiler 
water  returns to a suffi cient level.  In AUTO, the 
AquaSmart returns automatically.  In MAN (manual), the 
ENTER(RESET)
 button must be held for 5 seconds.