Beckett AQUASMART 7600 Manual De Usuario

Descargar
Página de 36
30
AquaSmart Operation
Table 4 – Typical operation with default settings (Circulator set “ON TT”)
System Action
AquaSmart Response
Temperature falls below low limit
Burner is turned on until the water temperature reaches the low 
limit plus the low differential.
ZC is turned off until the water temperature reaches the low limit 
plus the low differential.
Thermostat call for heat
Burner is turned on as long as the water temperature is below 
the high limit.
Circulator is turned on after circulator-on delay if the low limit is 
satisfi ed.
Thermostat is satisfi ed
Burner is turned off.
Circulator is turned off after circulator-off delay

ZR call for heat
Burner is turned on as long as the water temperature is below 
the high limit.
ZR is satisfi ed
Burner is turned off.
Temperature reaches high limit
Burner is turned off until the water temperature falls below the 
high limit minus the high differential.
Circulator is inactive for 3 days
Circulator is turned on for 2 seconds to help prevent seizure.
AquaSmart locks out
Burner, Circulator, and ZC are turned off until the control is 
reset.  The lockout condition may reset automatically or require 
a manual reset.  See lockout section for more information.
B1 has been energized for 1 hour or 
AquaSmart has been locked out for 1 hour
Circulator and ZC are turned on to help prevent system freeze-
up by circulating the boiler water to all zones.
Priority call for heat
If DHWP is set on T-T and there is a T-T call for heat, ZC is held 
off for up to 20 minutes to give the DHW zone priority.
If DHWP is set on ZR and there is a ZR call for heat, C1 is held 
off for up to 20 minutes to give the DHW zone priority.
Once the high limit is reached, the burner should turn off 
(C1 and ZC should now be energized, and B1 should be 
off).  The display should now read “CIRCULATING”.
Set the thermostat back, so that it is no longer calling for 
heat.  The circulator should turn off (now ZC should be 
energized and B1 and C1 should be off).  The display 
should now read “STANDBY”.
5.
6.
Do not leave the installation 
site if the AquaSmart 
operation did not match the descriptions in 
any of the above steps. Make all necessary 
adjustments until the correct operation is 
verifi ed. The above procedure helps to verify 
that the high and low limits are working 
properly and that the thermostat is wired 
correctly to the control.
Control Checkout Procedure
These procedures are typical for the default confi guration 
of the control.
Wire and confi gure the AquaSmart as required by the 
application.
NOTE: Do not apply a thermostat call for heat to the 
AquaSmart at this time. 
 Allow the burner to heat the 
water to above the low limit, plus the low limit differential.  
The display should read “HEATING WTR” on the LCD 
display (B1 should be energized and C1 and ZC should 
be off).  
When the water is suffi ciently heated, the burner will turn 
off and the display should read “STANDBY”.  Now ZC 
should be energized and B1 and C1 should be off.
Apply a call for heat from the thermostat.  The burner and 
circulator should now also turn on (B1, C1, and ZC should 
now all be energized).  Allow the AquaSmart to heat the 
water to the high limit.  During this step the display should 
read “HEATING WTR or “HEATING DHW”.
1.
2.
3.
4.