If you have a single stage compressor system see the dia-
gram below. A relay (customer provided) should be installed 
as shown in Fig 7 to switch the fan speed to the next lower 
speed on a call for dehumidifi cation from the thermostat. The 
reduction in air fl ow allows the coil to remove more humidity 
from the air. The relay should be rated for blower motor load. 
Since this confi guration reduces the air fl ow in cooling, the 
WIRING DIAGRAMS
anti-freeze-up control (White-Rodgers CAFC) or equivalent is 
recommended. The CAFC prevents the air conditioning coil 
from freezing due to low air fl ow, dirty fi lters, low refrigerant 
pressure, etc. The CAFC snaps onto the suction line close to 
the evaporator coil as possible and breaks the compressor 
circuit when the suction line drops below 38 °F and re-make 
the circuit at 46°F.
HOT
NEUTRAL
120 VAC
24 VAC
Relay
90-290Q
or equivalent 
HOT
NEUTRAL
120 VAC
TRANSFORMER
R
HM
Humidifier 
System
Figure 6 – Typical Wiring for 120V Humidifi er System
HOT
NEUTRAL
120 VAC
TRANSFORMER
HM
24 VAC
Humidifier 
System
R
Figure 7 – Typical Wiring for 24V Humidifi er System
Dehumidifi cation wiring without an electronically controlled variable speed blower system for 
single stage compressor system only. 
HM
DHM
Humidification Terminal, 
Energizes on call for 
heat if Humidity setpoint 
is above room humidity. 
Can also be used to 
provide humidification 
independent of a call for 
heat and/or in cooling 
mode if Automatic 
Humidification is 
selected in Configura-
tion Menu item #34
De-energizes on call for 
Dehumidification to 
lower the fan speed. 
The DHM terminal is 
only used on systems 
with a compatible 
dehumidification feature 
that have the required 
terminal connection on 
the contol module or 
have a relay installed to 
lower the fan speed
+
S
-
Supply voltage 
to remote 
temperature
sensor
Remote 
temperature 
sensor signal
Supply voltage 
to remote 
temperature
sensor
Figure 4 – Humidity and Sensors
 Relay 
90-293Q 
or equivalent
No
NC
“Heat Fan Output”
N
Dehum
Speed Fan
Med
DHM
N
Low
Normal High
“Cool Fan Output”
1
2
Normal Cool speed position (DHM energized)
Dehum speed mode (DHM de-energized)
1
2
Figure 5 – Typical Wiring for Dehumidifi er System