White Rodgers 1F82-261 White-Rodgers 80 Series Programmable Heat Pump Thermostat Instruccion De Instalación

Descargar
Página de 8
WARNING
!
Do not use on circuits exceeding specified voltage. 
Higher voltage will damage control and could cause 
shock or fire hazard.
Do not short out terminals on gas valve or primary 
control to test. Short or incorrect wiring will damage 
thermostat and could cause personal injury and/or 
property damage.
Thermostat installation and all components of the sys-
tem shall conform to Class II (current limited) circuits per 
the NEC code. Failure to do so could cause a fire hazard.
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY 
BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE 
PERSONAL INJURY AND/OR PROPERTY DAMAGE.
 DESCRIPTION
 
 SPECIFICATIONS
ELECTRICAL DATA
Electrical Rating: 
 
20 to 30 VAC 50/60 Hz. or D.C. 
 
0.05 to 1.0 Amps (Load per terminal) 
 
1.5 Amps Maximum Total Load (All terminals combined)
THERMAL DATA
Setpoint Temperature Range:
 
 
 
45°F to 90°F (7°C to 32°C) 
Operating Ambient Temperature Range: 
 
32°F to 105°F 
Operating Humidity Range: 
 
0 to 90% RH (non-condensing) 
Shipping Temperature Range: 
 
-4°F to 149°F
APPLICATIONS
For use with the following Class II systems:
•  Standard heat pump systems with electric, gas or oil Aux
heat with 24VAC Hot and Common available
•  Single-stage heat pump systems with no Aux heat with
24VAC Hot and Common available
DO NOT USE WITH:
•  Millivolt systems
•  Systems exceeding 30 VAC and 1.5 amps
•  3-wire zoned hydronic heating systems
1F82-261
Programmable Electronic Digital  
Heat Pump Thermostat
INSTALLATION AND
OPERATION INSTRUCTIONS
 
 PRECAUTIONS
This thermostat is intended for use with a low voltage NEC 
Class II system. Do not use this thermostat with a line voltage 
system. If in doubt about whether your wiring is millivolt, line,
or low voltage, have it inspected by a qualified heating and air
conditioning contractor or electrician.
Do not exceed the specification ratings.
All wiring must conform to local and national electrical codes 
and ordinances.
This control is a precision instrument, and should be handled
carefully. Rough handling or distorting components could cause 
the control to malfunction.
Operator:  Save these instructions for future use!
CAUTION
!
To prevent electrical shock and/or equipment damage, 
disconnect electric power to system at main fuse or 
circuit breaker box until installation is complete.
•  LCD continuously displays set point, and alternately
displays time and room temperature
•  Continuous Backlit display option
•  Temperature override until next program period
•  Manual program override (HOLD temperature)
•  Temporary HOLD
•  °F/°C convertibility
•  Temperature range 45° to 90°F
•  R, C, Y, W2, G, O/B, E, and L terminals for single or
two-transformer systems
Your new 5-Day/1-Day/1-Day Digital Thermostat uses the tech-
nology of a solid-state microcomputer to provide precise time/
temperature control. This thermostat offers you the flexibility to
design heating and cooling programs that fit your needs.
Features:
•  Separate 5-day (weekday) and 1-day/1-day (Saturday/
Sunday) programming with four separate time/temperature
periods per day
•  Simultaneous heat and cool program storage
•  Preprogrammed temperature control
•  Optional battery back-up for AC power loss
www.white-rodgers.com
www.emersonclimate.com
PART NO. 37-6175F
Replaces 37-6175E
1338