this displays the output voltage and current of the
battery you are charging. ( a less current but higher voltage )
( this is the setup information screen ) This screen gives different
information depending on the system cycle, it is informing you., WET OPEN= wet open lead acid cell batteries,
this shows that the system battery type dip switches are set for wet cell batteries,( 14.8 v max setting ) Bulk
charge refers to the initial charge rate, this could change to a timer, then adventually change to float ( float
charger 14 volts )
this shows that the system battery type dip switches are set for wet cell batteries,( 14.8 v max setting ) Bulk
charge refers to the initial charge rate, this could change to a timer, then adventually change to float ( float
charger 14 volts )
This screen shows the time left to the next pause cycle
( for 2.5 min. ) and that it is on auto. The auto can be removed by pushing buttons 1 and 2 together. This
removes the auto pause control, and the charger will still have all its safety and timing cycles, every 20 min.
pause
removes the auto pause control, and the charger will still have all its safety and timing cycles, every 20 min.
pause
R:v2.0 C:v2.0, this shows the software version for
remote ( R ) and for main PCB ( C ). the 12vIN-12vOUT, refers to the motel, a 12v-12v unit. There are 12-24 v,
24-24 and 24-12.
24-24 and 24-12.
: There are 2 x screens on this button. Push once for screen a, then
again for screen b. Screen a shows the alternator temp and the domestic battery temp, if the temperature
sensors are not fitted it will default to 20 deg C
sensors are not fitted it will default to 20 deg C
Temp 4a+b: There are 2 x screens on this button. Push once
for screen a, then again for screen b. Screen b shows the box heat sink temperatures, LHS stands for left hand
side, Guess what RHS stands for.
Do not expect these to be the same temperature
side, Guess what RHS stands for.
Do not expect these to be the same temperature
Pre set voltages:
Minimum input voltage the unit will run at 13 volts
Voltage the unit switches off and drops into sleep mode
below 12.8 v for at lease 15 mins
Power consumption on sleep mode. 5 ma ie 0.005 amps
max input voltage trip 15.5
max output voltage trip 15.5
Minimum input voltage the unit will run at 13 volts
Voltage the unit switches off and drops into sleep mode
below 12.8 v for at lease 15 mins
Power consumption on sleep mode. 5 ma ie 0.005 amps
max input voltage trip 15.5
max output voltage trip 15.5
Alt temp disengage 100 deg C
Reset alt 80
Battery temp trip 50 deg C
Heat sink trip 70 deg C
Heat sink reset 60 deg C
Fans on at 50 deg C
Fans on over 35 amps
Fans of at 45 deg C
Low battery alarm 1 2.5 v
Low battery regulation 13 v
high battery voltage trip 15.5v
Max input current at 12 v = 45 amps
amp meter +/- about 10%
voltmeter +/- 1%
Reset alt 80
Battery temp trip 50 deg C
Heat sink trip 70 deg C
Heat sink reset 60 deg C
Fans on at 50 deg C
Fans on over 35 amps
Fans of at 45 deg C
Low battery alarm 1 2.5 v
Low battery regulation 13 v
high battery voltage trip 15.5v
Max input current at 12 v = 45 amps
amp meter +/- about 10%
voltmeter +/- 1%
Push button marked 2 again: screen E/b
Screen F/a: Push button marked 3
Push button marked 3 again: screen F/b.
Push button marked 3 again: screen F/c.
Screen G/a: Push button marked 4.
Screen G/b:: Push button marked
( x 2 for 24 v models )
All voltages refer to a default temperature of 20 deg c
if the battery temperature sensor is fitted these voltages will be less depending on
the battery temperature