CAT Titan 250 Manual De Usuario

Descargar
Página de 81
Turbomachinery Package Specification 
Titan 
250 Generator Set 
Generator and Associated Equipment 
5.1 General 
Description 
For maximum flexibility, the gas turbine package can be provided with several different 
generator types and voltage outputs to accommodate a broad range of application 
requirements. The generator, exciter, and control system are integrated to provide 
optimal performance. 
The standard generator type supplied is open drip-proof (ODP) (Figure 6). However the 
following other enclosure types are available to meet a variety of environmental 
conditions and cooling requirements: 
•  Closed air circuit air cooled (CACA) 
•  Closed air circuit water-to-air cooled (CACW) 
•  Totally enclosed air-to-air cooled (TEAAC) 
•  Totally enclosed water-to-air cooled (TEWAC) 
 
 
Figure 6.  Typical Open Drip-Proof Generator with Permanent Magnet Exciter System 
5.2 Functional 
Description 
During generator operation, three-phase AC power generated by the exciter armature is 
converted to DC power by a rectifier. The DC output from the rectifier is applied as field 
excitation current to the generator rotor windings to create magnetic flux. The generator 
voltage output is controlled by the generator field current and the generator field current 
is controlled by a brushless exciter. The amount of DC current applied to the exciter field 
determines the exciter output voltage. A potential transformer senses the bus potential 
and provides a signal to the combined generator control module (CGCM) for excitation 
control. 
© 2008 Solar Turbines Incorporated. All rights reserved. 
TPS250GS/908 - Preliminary 
14