Turbomachinery Package Specification 
Titan 
250 Generator Set 
11 Enclosure 
11.1 General 
Description 
A driver-only or complete package enclosure can be provided as required. The enclosure 
housing (Figure 21) is a completely self-contained, weatherproof, insulated, and sound-
attenuated system. The enclosure is mounted on the package skid and supported by a 
heavy-duty frame. The enclosure sides include removable panels and/or doors to allow 
access to major components for inspection and maintenance and to permit removal of 
components by forklift or overhead crane. The engine area is furnished with bi-fold type 
doors to facilitate engine removal from either side of the package. All enclosure doors 
include a three-point heavy-duty door locking mechanism, handles, hinges, latching 
mechanism, internal lock override release, restraining device, and attaching hardware. 
The enclosure panels are treated with fiberglass material for sound attenuation and 
thermal insulation. Weather stripping is installed between all panels for sealing and sound 
attenuation. The enclosure is normally factory assembled on the package skid prior to 
shipment, but can be drop shipped pre-assembled for site installation or shipped as a kit 
for site assembly and installation. The following standard features are included with the 
basic enclosure: 
•  Inlet and exhaust ventilation silencers 
•  Single fan ventilation system 
•  Pressurization system 
•  AC lighting 
•  Equipment handling system 
•  Stainless steel door hardware 
 
 
Figure 21.  Typical Complete Package Enclosure 
© 2008 Solar Turbines Incorporated. All rights reserved. 
TPS250GS/908 - Preliminary 