Turbomachinery Package Specification 
Titan 
250 Generator Set 
large power source, protection against excessive kW load is provided by turbine T5 
temperature control. 
10.2.6  Generator Metering Panel (Optional) 
Mounted on the front of an optional control console, the generator metering panel (Figure 
20) provides meters to monitor generator output and switches to manually adjust 
generator voltage and to synchronize the generator breaker to the bus. The metering 
panel typically includes the following analog meters, lights, and switches: 
•  AC ammeter 
•  Frequency meter 
•  KW/kVAr meter 
•  AC voltmeter 
•  Power factor meter 
•  Synchroscope 
•  Exciter field ammeter 
•  Exciter field voltmeter 
•  Manual synchronizing lights 
•  Manual synchronizing switch 
•  Generator breaker Open/Close switch 
•  Generator breaker Open/Close status lights 
•  Automatic synchronization switch (optional) 
•  Automatic synchronization fail light (optional) 
•  Generator line-to-line voltmeter select switch 
•  Kilowatt (kW) and kilovolt amp reactive (kVAr) power meter select switch 
•  Generator phase current ammeter select switch 
All data indicated by the metering panel is also indicated on the video display terminal. 
 
 
 
© 2008 Solar Turbines Incorporated. All rights reserved. 
TPS250GS/908 - Preliminary 