Ducting Do’s and Don’ts
NEVER restrict the duct size. The island dual blower unit (T200) requires 8” round duct or 
equivalent (50 square inches). The island cluster blower unit (T400) requires 12” round or 
equivalent (113 square inches). Using the included Vent-A-Hood transition will ensure proper 
efficiency.
Do  not  use  flexible  or  corrugated  duct.  This  type  of  duct  will  restrict  airflow  and  reduce 
performance. Only use smooth, galvanized, metal duct. Observe local codes regarding special 
duct requirements and placement of duct against combustibles. Make the duct run as short 
and as straight as possible with as few turns as possible. Avoid sharp-angled turns. Instead, 
use smooth, gradual turns such as adjustable elbows or 45 degree angled turns. For duct runs 
over 20 feet, increase the duct diameter by one inch for every ten feet of duct. A 90 degree 
elbow is equal to 5 feet of duct. Using Vent-A-Hood roof jacks or wall louvers (back page) will 
ensure proper efficiency. Airflow must not be restricted at the end of the duct run. Do not use 
screen wire or spring-loaded doors on wall louvers or roof jacks. Do not terminate venting into 
an attic or chimney. Where possible, seal joints with duct tape. The hood must be ducted to the 
outdoors without restrictions.
Blower 
Duct Size 
Sq. Inch Area  Vent-A-Hood Transition
Island Dual (T200) 
8” round or equivalent 
50” 
VP565 (Included)
Island Cluster Blower (T400)  12” round or equivalent 
113” 
VP564 (Included)
YES
NO
Smooth Duct
Smooth Gradual Turn
Flexible Duct
Sharp Angled Turns