WALL CASE INSTALLATION – CORD SET CONNECTED
EXAMPLE: BLOCK 
AND 
VENEER – DIMENSIONAL DATA AND COMMENTS
ARE ALSO APPLICABLE TO OTHER TYPES OF CONSTRUCTION
*Caulk around perimeter of wall case all four sides
where it joins the building.
LINTEL
FINISHED
EXTERIOR WALL
FINISHED
INTERIOR
WALL
ADJACENT WALL
ADJACENT WALL
CAULK*
RAB71   13-3/4”
RAB77   13-7/8”
ROOM CABINET
CASE
RAB71   42”
RAB77   42-1/8”
A
D
D
C
2-1/2”
27-1/4”
TOP VIEW
ROOM CABINET
FRONT VIEW
See page 38 for line cord length.
WALL OPENING
16-1/4” x 42-1/4” MIN. FOR RAB71
16-1/2” x 42-3/8” MIN. FOR RAB77
ELECTRICAL RECEPTACLE (BY OTHERS).
FLUSH MOUNTED.
INSIDE
E
ROOM
CABINET
7-1/8”
MAX. WALL THICKNESS
13-1/8”
RAB71   13-3/4”
RAB77   13-7/8”
FINISH FLOOR
Caulk around
perimeter of wall case
all four sides where it
joins the building.
SIDE VIEW OF
ALTERNATE
HIGH MOUNT
With conduit
power supply.
A
16” RAB71
16-1/8” RAB77
B
Manufacturer Required
Dimension
Minimum Installation Clearance
A
1/4” (See note 1)
B
0” Min. (See page 26)
C
0” Minimum
D
0” Minimum 2” Recommended
See pages 35-36 for ducted applicaton.
E
3” Minimum
NOTE:
1. FOR OUTSIDE FLUSH MOUNTING SEE PAGE 34 FOR DRAIN INSTALLATION.