INSTALLATION PROCEDURE
2
PREPARING INDOOR UNIT
INSTALLATION
REMOVE THE INTAKE GRILLE AND SIDE COVER
(1) Remove the two Air filters.
(2) Remove the two Intake grilles.
• For 4 Left rear drain and 5 Left drain: Remove air filters and intake
grilles at three places. (Refer to “
2 INDOOR UNIT INSTALLATION”.)
(3) Remove the Side cover A (Right side) and Side cover B (Right and
Left side).
• For 5 Left drain : Remove both the Side cover A (Right and Left
side). (Refer to “
2 INDOOR UNIT INSTALLATION”.)
(4) This air conditioner can be set up to intake fresh air. For information
about how to install for fresh-air intake, refer to “
= FRESH-AIR INTAKE”.
INDOOR UNIT INSTALLATION
You can use the accessory template to help you install the indoor unit.
The template helps you determine the appropriate locations for suspen-
sion bolts and pipe opening (drain pipe and connection cord).
[For Half-Concealed Installation]
••••• Suspension-bolt pitch should be as shown in the figure.
2. SELECT PIPING DIRECTION
Select connection piping and drain piping directions.
[FOR
4 Left rear piping, 5 Left piping]
••••• Transfer the Drain cap and Drain cap seal.
Drain cap seal
Drain cap
Indoor unit
Drain pan
Drain cap seal
Drain cap
Push cap all the way on
(as far as it will go).
[If using anchor bolts]
(1) Drill holes for anchor bolts at the locations at which you will set the
suspension bolts. Note that anchor bolts are M10 bolts (to be ob-
tained locally).
(2) Install the anchor bolts, then temporarily attach special nut “B” (in-
cluded) and a locally-procured M10 nut to each of the bolts.
Anchor-Bolt Strength
980 to 1470 N (100 to 150 kgf)
4. INSTALLING THE INDOOR UNIT
(1) Lift unit so that suspension bolts pass through the suspension fittings
at the sides (four places), and slide the unit back.
Wall
Ceiling
Ceiling
M10 Anchor Bolt
(Obtained locally)
Special nut B
(Included)
M10 Nut
(Obtained locally)
10 to 15 mm
(3/8" to 19/32")
1. LOCATION OF CEILING SUSPENSION BOLTS
Suspension bolt pitch 1600 mm (63")
Dimensions
(Space Required
for Installation)
30 mm (1-3/16")
10 mm (3/8")
155 mm (6-3/32")
300 mm (12")
INDOOR UNIT (TOP VIEW)
INDOOR UNIT
Suspension bolt should
extend outward 30 to 75 mm.
(1-3/16" to 2-31/32")
30 mm (1-3/16")
3. DRILLING THE HOLES AND ATTACHING THE
SUSPENSION BOLTS
(1) Drill ø25 mm holes at the suspension-bolt locations.
(2) Install the bolts, then temporarily attach Special nuts A and B and a
normal M10 nut to each bolt. (The two special nuts are provided with
the unit. The M10 nut must be obtained locally.) Refer to the figure.
Bolt Strength
980 to 1470 N (100 to 150 kgf)
Ceiling panel
Special nut A (Included)
Special nut B (Included)
M10 Nut (Obtained locally)
10 to 15 mm
 (13/32" to 19/32")
INDOOR UNIT
Wall
Ceiling panel
(2) Fasten the indoor unit into place by tightening-up the special “B” bolts
and the M10 nuts. Make sure that unit is secure and will not shift back
and forth.
[For Half-Concealed Installation]
When installing the indoor unit in a semi-concealed orientation, make sure
to reinforce the insulation of the unit on all sides. Drops of water may fall
from the unit if it is not thoroughly insulated.
Glass wool insulate (10 to 20 mm
(3/8" to 3/4") thick)
INDOOR UNIT
(Top view)
Wall
Ceiling panel
 CAUTION
Install the drain pipe in accordance with the instructions
in this installation instruction sheet and keep the area
warm enough to prevent condensation. Problems with the
piping may lead to water leaks.
••••• Install the drain pipe with downward gradient (1/50 to 1/100) and so
there are no rises or traps in the pipe.
••••• Use general hard polyvinyl chloride pipe (VP25) [outside diameter
38 mm (1-1/2")].
••••• During installation of the drain pipe, be careful to avoid applying
pressure to the drain port of the indoor unit.
••••• When the pipe is long, install supporters.
••••• Do not perform air bleeding.
••••• Always heat insulate (8 mm (5/16") or over thick) the indoor side of the
drain pipe.
GOOD
BAD
BAD
Drain pipe
Arrange the drain pipe
lower than this portion.
Lifted up
Wave
End in water
Supporter
1.5 to 2 m
(5 to 6.5 ft)
(1) Install insulation for the drain pipe.
Cut the included insulation material to an appropriate size and adhere
it to the pipe.
Drain pipe
Insulation for drain pipe
(To be obtained locally. Length
should be at least 8 mm (5/16").)
Drain pipe insulation (accessories)
Indoor unit (drain port)
(2) If “
1 Right rear piping” : fasten the drain pipe with VT wire so that the
pipe slopes correctly within the indoor unit.
Indoor unit (rear view)
VT wire
Drain hose
Drain pipe insulation
Drain pipe
No gap
10 mm (3/8") or over
Indoor unit
1 Right rear piping
5 Left piping
(Drain pipe only)
4 Left rear piping
(Drain pipe only)
2 Top piping
(Connection pipe only)
3 Right
piping
Cut off the piping outlet cutting groove
with a hacksaw, etc.
INDOOR UNIT (TOP VIEW)
Air filter
Intake grille
Tapping screw
INDOOR UNIT
Side cover A (Right side)
Side cover B
(Left side)
Side cover B (Right side)
Drilling position for Suspension bolt
Ceiling
Wall
Template
Drilling position for piping
Ceiling Opening: 1580 mm (62")
40 mm (1-9/16")
Ceiling panel
Ceiling Opening: 640 mm (25-3/16")
15 mm (19/32")
Suspension bolt should
extend outward 30 to 50 mm.
(1-3/16" to 1-31/32")
INDOOR UNIT
Ceiling panel
40 mm (1-9/16")
 CAUTION
In order to check the drainage, be sure to use a level
during installation of the indoor unit. If the installation site
of the indoor unit is not level, water leakage may occur.
5. DRAIN PIPING