D9412GV3/D7412GV3 | Program Entry Guide | 5.0  AUXPARM 
EN | 137 
 
 
Bosch Security Systems, Inc. | 10/11 | F01U170807-02 
 
5.8 Miscellaneous 
Fire Summary Sustain 
Default: 
No 
Selection: 
Yes or No 
Yes 
Forces the Summary Fire relay 
output to remain on after the Alarm 
Silence command. 
No 
Allows Summary Fire relay output 
to be silent when the Fire Alarm Bell 
output is silenced and all Fire Points 
return to normal. 
Use this parameter to set the Summary Fire relay 
output to continue or to stop after the Fire Alarm Bell 
is silenced or times out. Refer to the Summary Fire 
prompt in Section 2.12.2 Panel-Wide Relays on 
page 82. 
Fire Supervision Restoral Type 
Default: 
Selection: 
0, 1, 2 
The control panel sends a FIRE 
TROUBLE RESTORE when a Fire 
Supervision point restores to normal. 
The control panel sends a FIRE 
ALARM RESTORE when a Fire 
Supervision point restores to normal. 
The control panel sends a FIRE 
SUPERVISION RESTORE when a 
Fire Supervision point restores to 
normal. 
Determines how the control panel sends a Fire 
Supervision Restoral Event. 
 
The Fire Supervision Restore Event is 
part of Fire Events in Routing. If Fire 
Supervision Restore Events are needed, 
simply enable them in Routing. 
Early Ambush Timer 
Default: 
10 min 
Selection: 
5 to 30 min 
The programmed time is the maximum value of the 
Early Ambush Timer. When Early Ambush is set to 
Yes for a specified area (refer to A# Early Ambush on 
page 48) and the area is disarmed, the user has the 
amount of time programmed here to enter a second 
code into the keypad. 
If a second passcode is not entered within the 
programmed time, a Duress event is generated 
based on the first user code. Duress reports must be 
enabled in Routing in order to be sent to a central 
station.  
Secondary Ambush Code 
Default: 
Unique 
Selection: 
Unique or any 
Unique 
The code used to end the timer must 
be different from the code used to 
disarm the area. 
Any 
The timer can be stopped using a 
different code, or the same code that 
disarmed the area. 
The Secondary Ambush Code determines whether 
the same passcode can be used to begin and end 
the Early Ambush process. 
 
Abort Window 
Default: 
30 sec 
Selection:  15 to 45 sec 
 
This parameter determines the amount of time the 
control panel delays a Burglar Alarm event from a 
point with P## Alarm Abort set to Yes. If an alarm 
silence operation is performed before this time 
elapses, the alarm transmission is aborted and the 
keypad shows an optional ALARM NOT SENT 
message. When an alarm transmission is 
successfully aborted, no event is written to the control 
panel event log. 
When an abort alarm timer starts, it does not stop 
until an alarm silence operation is performed or the 
time expires. 
 
This feature does not apply to Fire Alarms 
or invisible point alarms.