PowerLogic ION7550 / ION7650 Installation Guide
12 
© 2007 Schneider Electric.  All rights reserved.
Step 4: Wire the Voltage and Current Inputs 
Voltage Inputs
Current Inputs: Class 20 Current Inputs (5A Option)
Current Inputs: Class 2 Current Inputs (1A Option)
N
OTE
The appropriate Volts Mode setting is included with each wiring diagram.
Refer to Step 8 to learn how to configure Volts Mode on the meter.
3~  VOLTAGE INPUTS
3~  CURRENT INPUTS
V
3
V
4
V
ref
I
11
I
12
I
21
I
22
I
31
I
32
I
41
I
42
I
51
V
1
V
2
I
52
Connector Type
Ring or split ring connector
Wire Gauge
3.3 to 2.1 mm
2
 (12 to 14 AWG)
Rated Inputs
347 V L-N RMS /600 V L-L RMS
Fault Capture
1200 V L-N peak
Overload
1500 VAC RMS continuous
Dielectric Withstand
2500 VAC RMS at 60 Hz for 60 s
Input Impedance
5 MΩ/phase (phase - Vref)
Connector Type
Ring or split ring connector
Wire Gauge
5.3 to 3.3 mm
2
 (10 to 12 AWG):
Use 8.4 mm
2
 (8 AWG) for 10-20 A applications 
Input Rating
5 A, 10 A, and/or 20 A RMS
Starting Current
0.005 A RMS
Fault Capture
70 A peak
Max. Voltage
600 V RMS (CAT III IEC61010-1)
Overload
500 A RMS for 1 s, non-recurring
Dielectric Withstand
2500 VAC RMS at 60 Hz for 60 s
Burden
0.05 VA per phase (at 5 A)
Impedance
0.002 Ω per phase
Connector Type
Ring or split ring connector
Wire Gauge
5.3 to 3.3 mm
2
 (10 to 12 AWG)
Input Rating
1 A, 2 A, 5 A, and/or 10 A RMS
Starting Current
0.001 A RMS
Fault Capture
17.5 A peak
Max. Voltage
600 V RMS (CAT III IEC61010-1)
Overload
50 A RMS for 1s, non-recurring
Dielectric Withstand
2500 VAC RMS at 60 Hz for 60 s
Burden
0.015 VA per phase (at 1 A)
Impedance
0.015 Ω per phase