Schneider Electric ION7650 Manual De Usuario

Descargar
Página de 28
PowerLogic ION7550 / ION7650 Installation Guide
© 2007 Schneider Electric.  All rights reserved.
 13
4-Wire Wye, 3-Element, Direct Connection Diagram
347 V L-N / 600 V L-L max.
VOLTS MODE = 4W-Wye
4-Wire Wye, 3-Element, 3 PTs Connection Diagram 
Use PTs for voltages over 347 V L-N / 600 V L-L.
Wye (Star) wiring for PT primaries and secondaries.
VOLTS MODE = 4W-Wye
4-Wire Wye, 2½-Element, 2 PTs Connection 
  
Phase B voltage (V2) displayed by meter is derived from phase A and 
phase C, not measured. V2 will display a value even if no voltage is 
present on Phase B. V2 values are only accurate for balanced loads.
VOLTS MODE = 3W-Wye
LINE
LO
A
D
Fuse for N/- terminal 
required if its supply 
source is ungrounded 
Connect G terminal
to ground for AC 
power source
I4 Optional
LINE
LO
A
D
Fuse for N/- terminal 
required if its supply 
source is ungrounded 
Connect G terminal
to ground for AC 
power source
I4 Optional
LINE
LOAD
Fuse for N/- terminal 
required if its supply 
source is ungrounded 
Connect G terminal
to ground for AC 
power source
I4 Optional