Adjustment of the output torque 
(current) of the motor
4.8 Adjustment of the output torque (current) of the motor
4.8.1
Manual torque boost (Pr. 0, Pr. 46, Pr. 112)
(1) Starting torque adjustment
⋅ On the assumption that Pr. 19 Base frequency voltage is 100%, set the output voltage at 0Hz in % in Pr. 0 (Pr. 46, Pr. 112).
⋅ Adjust the parameter little by little (about 0.5%), and check the motor status each time. If the setting is too large, the
motor will overheat. The guideline is about 10% at the greatest.
 
Purpose
Parameter that must be Set
Refer to Page
Set starting torque manually
Manual torque boost
Pr. 0, Pr. 46, Pr. 112
Automatically control output current 
according to load
Advanced magnetic flux 
vector control
Pr. 71, Pr. 80, Pr. 81, Pr. 89, Pr. 450, 
Pr. 451, Pr. 453, Pr. 454, 
Pr. 569, Pr. 800
Compensate for motor slip to secure 
low-speed torque
Slip compensation
Pr. 245 to Pr. 247
Limit output current to prevent inverter 
trip
Stall prevention operation
Pr. 22, Pr. 23, Pr. 66, 
Pr. 154, Pr. 156, Pr. 157
You can compensate for a voltage drop in the low-frequency region to improve motor torque reduction in the low-
speed range.
Motor torque in the low-frequency range can be adjusted to the load to increase the starting motor torque.
Three types of starting torque boost can be changed by switching terminals.
Parameter 
Number
Name
Initial Value
Setting 
Range
Description
0
Torque boost
0.4, 0.75K
6%
0 to 30%
Set the output voltage at 0Hz as %.
1.5K to 3.7K
4%
5.5K, 7.5K
3%
11K to 55K
2%
75K or higher
1%
46
Second torque 
boost
9999
0 to 30%
Set the torque boost value when the 
RT signal is ON.
9999
Without second torque boost
112
Third torque 
boost
9999
0 to 30%
Set the torque boost value when the 
X9 signal is ON.
9999
Without third torque boost
V/F
V/F
V/F
Output 
voltage
Pr.0
Pr.46
Setting 
range
Base 
frequency
0
100%
Output 
frequency
(Hz)
Pr.112