(current) of the motor
4.8.3
Slip compensation (Pr. 245 to Pr. 247)
⋅ Slip compensation is validated when the motor rated slip calculated by the following formula is set in Pr. 245. Slip
compensation is not made when Pr. 245 = "0" or "9999".
The inverter output current may be used to assume motor slip to keep the motor speed constant.
Parameter 
Number
Name
Initial Value
Setting Range
Description
245
Rated slip
9999
0.01 to 50%
Used to set the rated motor slip.
0, 9999
No slip compensation
246
Slip compensation time 
constant
0.5s
0.01 to 10s
Used to set the slip compensation response 
time. When the value is made smaller, 
response will be faster. However, as load 
inertia is greater, a regenerative overvoltage 
fault (E.OV ) is more liable to occur.
247
Constant-power range slip 
compensation selection
9999
0
Slip compensation is not made in the 
constant power range (frequency range 
above the frequency set in Pr. 3)
9999
Slip compensation is made in the constant 
power range.
Rated slip
=
Synchronous speed at base frequency - rated speed × 100[%]
Synchronous speed at base frequency
REMARKS
When performing slip compensation, the output frequency may become greater than the set frequency. Set the Pr. 1 Maximum
frequency
 value a little higher than the set frequency.