152
Adjustment of the output torque 
4.8.4
Stall prevention operation (Pr. 22, Pr. 23, Pr. 48, Pr. 49, Pr. 66, Pr. 114, Pr. 115, 
Pr. 148, Pr. 149, Pr. 154, Pr. 156, Pr. 157, Pr. 858, Pr. 868)
*
This parameter allows its setting to be changed during the operation in any operation mode even if "0 (initial value) or 1" is set in Pr.77 Parameter
write selection
.
 
This function monitors the output current and automatically changes the output frequency to prevent the inverter
to trip due to overcurrent, overvoltage, etc. It can also limit stall prevention and fast response current limit
operation during acceleration/deceleration, driving or regeneration. Invalid under Real sensorless vector control
or vector control.
Stall prevention
If the output current exceeds the stall prevention operation level, the output frequency of the inverter is
automatically varied to reduce the output current.
Also the second stall prevention function can restrict the output frequency range in which the stall prevention
function is valid. (Pr. 49)
Fast response current limit
If the current exceeds the limit value, the output of the inverter is shut off to prevent an overcurrent.
Parameter 
Number
Name
Initial Value
Setting 
Range
Description
22
*
Stall prevention operation 
level
150%
0
Stall prevention operation selection becomes invalid.
0.1 to 400%
Set the current value at which stall prevention 
operation will be started.
23
Stall prevention operation 
level compensation factor 
at double speed
9999
0 to 200%
The stall operation level can be reduced when 
operating at a high speed above the rated frequency.
9999
Constant according to Pr. 22
48
Second stall prevention 
operation current
150%
0
Second stall prevention operation invalid
0.1 to 220%
The second stall prevention operation level can be set.
49
Second stall prevention 
operation frequency
0Hz
0
Second stall prevention operation invalid
0.01 to 400Hz
Set the frequency at which stall prevention operation 
of Pr. 48 is started.
9999
Pr. 48 is valid when the RT signal is ON.
66
Stall prevention operation 
reduction starting frequency
60Hz
0 to 400Hz
Set the frequency at which the stall operation level 
starts being reduced.
114
Third stall prevention 
operation current
150%
0
Third stall prevention operation invalid
0.1 to 220%
Stall prevention operation level can be changed with 
the X9 signal.
115
Third stall prevention 
operation frequency
0Hz
0
Third stall prevention operation invalid
0.01 to 400Hz
Set the frequency at which stall prevention operation 
when the X9 signal is ON starts.
148
Stall prevention level at 
0V input
150%
0 to 220%
Stall prevention operation level can be changed by 
the analog signal input to terminal 1 (terminal 4).
149
Stall prevention level at 
10V input
200%
0 to 220%
154
Voltage reduction 
selection during stall 
prevention operation
1
0
With voltage 
reduction
You can select whether to use 
output voltage reduction 
during stall prevention 
operation or not.
1
Without voltage 
reduction
156
Stall prevention operation 
selection
0
0 to 31,
100, 101
You can select whether stall prevention operation and 
fast response current limit operation will be performed 
or not.
157
OL signal output timer
0s
0 to 25s
Set the output start time of the OL signal output when 
stall prevention is activated.
9999
Without the OL signal output
858
Terminal 4 function 
assignment
0
0, 1, 4, 9999
By setting "4", the stall prevention operation level can 
be changed with a signal to terminal 4.
868
Terminal 1 function 
assignment
0
0 to 6, 9999
By setting "4", the stall prevention operation level can 
be changed with a signal to terminal 1.
(1) Setting of stall prevention operation level (Pr. 22)
⋅ Set in Pr. 22 the ratio of the output current to the rated inverter current at 
which stall prevention operation will be performed. Normally set 150% 
(initial value).
⋅ Stall prevention operation stops acceleration (makes deceleration) during 
acceleration, makes deceleration during constant speed, and stops 
deceleration during deceleration.
⋅ When stall prevention operation is performed, the OL signal is output.
V/F
V/F
V/F
Magnetic flux
Magnetic flux
Magnetic flux
Stall prevention operation example
Pr. 22
OL
Output current
Output frequency
Acceleration
Constant 
speed
Deceleration
Time