Schneider Electric HRB1684301-01 Manual De Usuario

Descargar
Página de 148
130
HRB1684301-01
Chapter 15—Verifying accuracy
PowerLogic™ PM5500 series user manual
6. Depending on the method selected for counting the energy pulses, configure the 
meter’s alarm / energy LED or one of the digital outputs to perform energy pulsing. 
Set the meter’s energy pulse constant so it is in sync with the reference test 
equipment.
7. Perform accuracy verification on the test points. Run each test point for at least 30 
seconds to allow the test bench equipment to read an adequate number of pulses. 
Allow 10 seconds of dwell time between test points.
Calculating the number of required pulses
The reference test equipment typically requires you to specify the number of pulses 
required for a test duration of “t” seconds. Normally, the number of pulses required is at 
least 25 pulses, and the test duration is greater than 30 seconds.
Use the following formula to calculate the required number of pulses:
Where:
Ptot = total instantaneous power in kilowatts (kW)
K = the meter’s pulse constant setting, in pulses per kWh
t = test duration, in seconds (typically greater than 30 seconds)
Calculating total power
The test voltage and current source supplies the same test signals to both the energy 
reference/standard and the meter under test. Total power is calculated as follows:
For a balanced 3-phase Wye system:
NOTE: A balanced 3-phase system assumes the voltage, current and power factor 
values are the same for all phases.
For a single-phase system:
Where:
Ptot = total instantaneous power in kilowatts (kW)
VLN = test point line-to-neutral voltage in volts [V]
I = test point current in amps [A]
PF = power factor
The result of the calculation is rounded up to the nearest integer.
Percent error calculation
For every test point:
Number of pulses 
Ptot K
t
3600
------------
=
Ptot
3 VLN I PF
1 kW
1000 W
-------------------
=
Ptot
VLN I
PF
1 kW
1000 W
-------------------
=
Energy Error
EM ES
ES
---------------------- 100
%
=