Chapter 15—Verifying accuracy
HRB1684301-01
131
Where:
EM = energy measured by the meter under test
ES = energy measured by the reference device or energy standard.
NOTE: If accuracy verification reveals inaccuracies in your meter, they may be caused 
by typical sources of test errors. If there are no sources of test errors present, please 
contact your local Schneider Electric representative.
Related topics
Test points
The meter should be tested at full and light loads and at lagging (inductive) power 
factors to help ensure testing over the entire range of the meter. The test amperage and 
voltage input rating are labeled on the meter. Refer to the installation sheet or data 
sheet for your meter’s nominal current, voltage and frequency specifications.
Energy pulsing considerations
The meter’s alarm / energy LED and digital outputs are capable of energy pulsing within 
the following limits:
The pulse rate depends on the voltage, current and PF of the input signal source, the 
number of phases, and the VT and CT ratios.
If Ptot is the instantaneous power (in kW) and K is the pulse constant (in pulses per 
kWh), then the pulse period is:
Watt-hour test points example
Watt-hour test point
Sample accuracy verification test point
Full load
100% to 200% of the nominal current, 100% of the nominal voltage and nominal 
frequency at unity power factor or one (1).
Light load
10% of the nominal current, 100% of the nominal voltage and nominal frequency 
at unity power factor or one (1).
Inductive load (lagging 
power factor)
100% of the nominal current, 100% of the nominal voltage and nominal frequency 
at 0.50 lagging power factor (current lagging voltage by 60° phase angle).
Var-hour test points example
Var-hour test point
Sample accuracy verification test point
Full load
100% to 200% of the nominal current, 100% of the nominal voltage and nominal 
frequency at zero power factor (current lagging voltage by 90° phase angle).
Light load
10% of the nominal current, 100% of the nominal voltage and nominal frequency 
at zero power factor (current lagging voltage by 90° phase angle).
Inductive load (lagging 
power factor)
100% of the nominal current, 100% of the nominal voltage and nominal frequency 
at 0.87 lagging power factor (current lagging voltage by 30° phase angle).
Energy pulsing limits
Description
Alarm / energy LED
Digital output
Maximum pulse frequency
2.5 kHz
25 Hz
Minimum pulse constant
1 pulse per kWh
Maximum pulse constant
9,999,999 pulses per kWh
Pulse period (in seconds)
3600
K Ptot
--------------------
1
Pulse frequency (Hz)
---------------------------------------------------
=
=