Chapter 17—MID compliance
PowerLogic™ PM5500 series user manual
Meter firmware version
You can access information about the meter’s OS and RS firmware versions by 
navigating to Maint > Setup > Diag > Info. The OS CRC value is a number that 
identifies the uniqueness between different OS firmware versions.
NOTE: For MID compliance, the meter’s firmware upgrade functionality is permanently 
disabled. You cannot upgrade a PM5561 meter’s firmware.
Related topics
MID-protected setup parameters
This section describes the setup parameters that are permanently set at the factory and 
cannot be modified, regardless of the lock or unlock settings.
The alarm / energy pulsing LED on the meter is permanently set for energy pulsing and 
cannot be disabled or used for alarms. All other setup parameters for the energy 
pulsing LED are also permanently set and cannot be modified.
NOTE: The pulses per kWh reflect uncompensated values only. This means that the 
PT and CT values are ignored and the pulses represent the raw energy calculated from 
the metering inputs.
Lock-protected setup parameters
This section lists the meter’s lock-protected setup parameters for MID compliance. After 
the meter is locked, these setup parameters are protected and cannot be edited.
The setup parameters can be accessed from the maintenance menu screen. Use the 
front panel buttons to navigate to the Maint > Setup menu.
Front panel LEDs 
Alarm / energy pulsing LED (orange)
Heartbeat / communications LED (green)
MID-protected setup parameters 
Setup menu
Setup submenu
MID-protected setup parameter
I/O
LED
Mode (Control) = Energy (energy pulsing)
Pulses per k_h (Pulse Rate) = 10,000 (pulses 
per kWh)
Channel (Parameter) = Active Energy Del+Rec