PowerLogic™ PM5500 series user manual 
Chapter 3—Front panel display and meter setup
HRB1684301-01
37
7. Press Yes to save your changes.
Related topics
Configuring advanced setup parameters
The advanced setup screens let you configure the following:
Load timer setpoint: defines the active load current, which is the minimum input 
current required to start and keep the active load timer counting.
Peak current demand for total demand distortion: specifies the minimum current 
demand value required to include in total demand distortion calculations.
1. Navigate to Maint > Setup.
2. Enter the setup password (default is “0”), then press OK.
3. Navigate to Meter > Advan.
4. Move the cursor to point to the parameter you want to modify, then press Edit.
5. Modify the parameter as required, then press OK.
6. Move the cursor to point to the next parameter you want to modify, press Edit
make your changes, then press OK.
7. Press Yes to save your changes.
Sys Frequency (Hz)
50, 60
Select the frequency of the electrical power 
system, in Hz.
Phase Rotation
ABC, CBA
Select the phase rotation of the 3-phase system.
Basic setup parameters (Continued)
Parameter
Values
Description
Advanced setup menu tree
Advanced setup parameters 
Parameter
Values
Description
Label
This label identifies the device, e.g., “Power 
Meter”. You cannot use the front panel to edit 
this parameter. Use ION Setup to change the 
device label.
Load Timer Setpt (A)
0 - 9
Specifies the minimum average current at the 
load before the timer starts. The meter begins 
counting the number of seconds the load timer 
is on (i.e., whenever the readings are equal to 
or above this average current threshold.
Pk I dmd for TDD (A)
0 - 9
Specifies the minimum peak current demand 
at the load for inclusion in total demand 
distortion (TDD) calculations. If the load 
current is below the minimum peak current 
demand threshold, the meter does not use the 
readings to calculate TDD. Set this to “0” 
(zero) if you want the power meter to use the 
metered peak current demand for this 
calculation.
Maint
Reset
Setup
Basic
Adv
Dmd
Tariff
Meter