Schneider Electric HRB1684301-01 Manual De Usuario

Descargar
Página de 148
78
HRB1684301-01
Chapter 8—Input / Output
PowerLogic™ PM5500 series user manual
Configuring digital outputs using the front panel
You can use the front panel to configure the digital outputs.
1. Navigate to Maint > Setup.
2. Enter the setup password (default is “0”), then press OK.
3. Navigate to I/O > D Out.
4. Move the cursor to point to the digital output you want to set up, then press Edit.
5. Move the cursor to point to the parameter you want to modify, then press Edit.
NOTE: If Edit is not displayed, it means the parameter is either read-only or can only 
be modified through software.
6. Modify the parameter as required, then press OK.
7. Move the cursor to point to the next parameter you want to modify, press Edit
make your changes, then press OK.
8. Press   to exit. Press Yes to save your changes.
Select Alarms
Over Current, Ph; Under 
Current, Ph; Over Current, 
N; Over Current, Gnd; Over 
Voltage, L-L; Under 
Voltage, L-L; Over Voltage, 
L-N; Under Voltage L-N; 
Over kW; Over kVAR; Over 
kVA; Lead PF, True; Lag 
PF, True; Lead PF, Disp; 
Lag PF, Disp; Over kW 
Dmd, Pres; Over kW Dmd, 
Last; Over kW Dmd, Pred; 
Over kVAR Dmd,Pres; Over 
kVAR Dmd,Last; Over 
kVAR Dmd,Pred; Over kVA 
Dmd, Pres; Over kVA Dmd, 
Last; Over kVA Dmd, Pred; 
Over Frequency; Under 
Frequency; Over Voltage 
Unbal; Over Voltage THD; 
Phase Loss; Meter 
Powerup; Meter Reset; 
Meter Diagnostic; Phase 
Reversal; Digital Alarm S1 
through S4; Custom Alarm 
1 through 5; Logic Alarm 1 
through 10
Applies when Control Mode is set to Alarm. Select 
one or more alarms to monitor.
Associations
This field displays additional information if the digital 
output is already associated with another meter 
function.
Digital output setup menu tree
Digital output setup parameters available through ION Setup (Continued)
Parameter
Values
Description