Chapter 8—Input / Output
PowerLogic™ PM5500 series user manual
Energy pulsing
You can configure the meter’s alarm / energy LED or one of the digital outputs for 
energy pulsing applications.
NOTE: The alarm / energy pulsing LED on the PM5561 is permanently set for energy 
pulsing and cannot be disabled or used for alarms.
When the LED is set to energy pulsing, the meter sends a readable pulse or signal 
based on the measured energy. This pulse can be used for accuracy verification or as 
an input to another energy monitoring system. The meter uses the pulse constant 
setting in pulses per k_h to determine the frequency and number of pulses sent to the 
LED (where k_h = kWh, kVARh or kVAh depending on the energy parameter selected).
The LED setup screen allows you to configure the alarm / energy pulsing LED for 
alarming or energy pulsing applications.
Configuring the alarm / energy pulsing LED using the front panel
You can use the front panel display to configure your meter’s LED for alarming or 
energy pulsing application.
1. Navigate to Maint > Setup.
2. Enter the setup password (default is “0”), then press OK.
3. Navigate to I/O > LED.
4. Move the cursor to point to the parameter you want to modify, then press Edit.
Location of alarm / energy pulsing LED 
PM5560, PM5561
PM5563
A
Alarm / energy pulsing LED
Alarm / energy pulsing LED settings menu tree
Maint
Reset
Setup
LED
D In
D Out
Inp Mtr
Comm
Alarm
I/O
Meter