PowerLogic™ PM5300 series 
Chapter 15—MID Compliance
© 2014 Schneider Electric All Rights Reserved
111
Setting up the PM5331/PM5341
You must configure all the lock-protected setup parameters before locking the meter. 
When the meter is locked, those setup parameters cannot be edited.
Basic setup menu
For MID compliance, the Power System must be set to one of the following settings:
3PH4W Wye Gnd (three-phase 4-wire wye grounded)
3PH3W Wye Ungnd (three-phase 3-wire wye ungrounded)
Advanced setup menu
See “Advanced setup” on page 41 to perform advanced setup.
You must use ION Setup to edit the device label.
Clock setup menu
See “Setting the clock” on page 41 to change the meter time using the display.
You can also use ION Setup to set or sync the meter time.
Tariff setup menu
Passwords setup menu
See “Setting up the screen passwords” on page 39 to change the meter screen 
passwords.
Initializing the meter
Initializing the meter clears the meter’s logged data, counters and timers. It is common 
practice to initialize the meter after its configuration is complete, before adding it to an 
energy management system.
1. After configuring all the meter setup parameters, navigate through the different 
meter display screens and make sure the displayed data is valid.
2. See “Meter resets” on page 99 for instructions on clearing the meter’s recorded 
logged data, counters and timers.
3. Select Meter Initialization to clear all recorded data.
Lock-protected functions
Menu
Sub-menu
Lock-protected function
Resets
Global Resets
Meter Initialization (all)
Energies
Single Resets
Energy
Multi-Tariff