Chapter 5—Viewing Meter Data
PowerLogic™  PM5300 series user guide
Related topics
Related topics
Related topics
Related topics
Volts [U-V]
V L-L [U]
Line-to-line voltage for each phase.
V L-N [V]
Line-to-neutral voltage for each phase.
Harm
V L-L [U]
Line-to-line voltage harmonics data: Numeric magnitude and 
angle for the fundamental harmonic, and graphical 
representation of harmonics for the 3rd to 11th, 13th to 21st, and 
23rd to 31st odd harmonics for each line-to-line phase voltage.
Fund, 3-11, 13-21, 23-31
V L-N [V]
Line-to-neutral voltage harmonics data: Numeric magnitude and 
angle for the fundamental harmonic, and graphical 
representation of harmonics for the 3rd to 11th, 13th to 21st, and 
23rd to 31st odd harmonics for each line-to-neutral phase 
voltage.
Fund, 3-11, 13-21, 23-31
Amps [I]
Current harmonics data: Numeric magnitude and angle for the 
fundamental harmonics, and graphical representation of 
harmonics for the 3rd to 11th, 13th to 21st, and 23rd to 31st odd 
harmonics for each phase current.
Fund, 3-11, 13-21, 23-31
TDD
Total demand distortion for each phase voltage.
Power [PQS]
Power [PQS]
Summary of real-time power consumption values for total active 
power [Ptot] in kW, total reactive power [Qtot] in kVAR, and total 
apparent power [Stot] in kVA.
Phase
Per phase (A [P1], B [P2], C [P3]) and total (Total [Ptot]) power 
values for active power in kW, reactive power in kVAR and 
apparent power in kVA.
Active [P], Reac [Q], Appr [S]
Dmd
Summary of peak power demand values in the previous (Last) 
demand interval period for active power in kW, reactive power in 
kVAR and apparent power in kVA.
Wd [Pd], VARd [Qd], VAd [Sd]
Total and per phase (A [1], B [2], C [3]) peak power demand 
values in the previous (Last) demand interval for active power 
demand (Wd [P]), reactive power demand (VARd [Q]) and 
apparent power demand (VAd [S]).
Tot, A [P1], B [P2], C [P3]
Each of these sub-screens (total and per phase demand) display 
power demand values for the current (Pres) demand interval, 
predicted (Pred) demand based on the current power 
consumption rate, demand for the previous (Last) demand 
interval period, and the recorded peak (Peak) power demand 
value.
Pk DT
Date and timestamp for the peak (Peak) power demand value.
Energy [E]
Wh
Delivered (Del), received (Rec), delivered minus received (D+R) 
and delivered minus received (D-R) accumulated values for real 
energy (Wh), apparent energy (VAh) and reactive energy 
(VARh).
VAh
VARh
Tariff
Displays the available tariffs (T1 through T4).
T1, T2, T3, T4
Del
Real (Wh), reactive (VARh) and apparent (VAh) energy delivered 
values for the selected tariff.
Rec
Real (Wh), reactive (VARh) and apparent (VAh) energy received 
values for the selected tariff.