Chapter 4—Front panel display and meter setup
PowerLogic™  PM5300 series user guide
8. Press Yes to save your changes.
Multi-tariff setup
The meter’s multi-tariff feature allows you to use up to 4 different tariff “containers” to 
store accumulated energy data. The Tariff setup screens allow you to configure how 
and when to apply the different tariffs.
Related topics
See “Configuring tariffs using the front panel” on page 87 for a comprehensive 
description and setup instructions using the front panel.
Alarms setup
An alarm is the meter’s means of notifying you when an alarm condition is detected, 
such as an error or event that falls outside of normal operating conditions.
Related topics
See “Alarms” on page 63 for a comprehensive description and detailed setup 
instructions.
Remote Meter Setup
You can use ION Setup to remotely access the meter. 
For more information on the ION setup configuration, please refer to ION Setup 3.0 
Device configuration guide.
Subinterval (min)
0 - 60
Applies only to rolling block methods.
Define how many subintervals the demand 
interval should be equally divided into.
Select Dig Output
None, Digital Output D1, Digital 
Output D2
Select which digital output the end of 
demand interval pulse should be sent to.
Select S Input
None, Status Input S1, Status Input 
S2
Applies only to input block methods.
Select which status input is used to monitor 
input metering demand.
Clock Sync Time
0 - 2359
Applies only to clock sync methods (these 
synchronize the demand interval to the 
meter’s internal clock).
Define what time of day you want to 
synchronize the demand
Power or current demand setup parameters (continued)
Parameter
Values
Description