PowerLogic™  PM5300 series user guide 
Chapter 6—Input / Output
© 2014 Schneider Electric All Rights Reserved
59
Configuring relay outputs using the front panel
You can use the front panel to configure the relay outputs.
1. Navigate to Maint > Setup.
2. Enter the setup password (default is “0”), then press OK.
3. Navigate to I/O > Relay.
4. Move the cursor to point to the relay output you want to set up, then press Edit.
5. Move the cursor to point to the parameter you want to modify, then press Edit.
NOTE:
If Edit is not displayed, it means the parameter is either read-only or can only 
be modified through software.
6. Modify the parameter as required, then press OK.
7. Move the cursor to point to the next parameter you want to modify, press Edit
make your changes, then press OK.
8. Press   to exit. Press Yes to save your changes.
Relay output setup menu tree
Relay output setup parameters available through the front panel
Parameter
Values
Description
Label
-----
This can be modified only through software. Use this 
field to change the default label and assign a 
descriptive name to this relay output.
Control Mode
External, Alarm
This displays how the relay output functions.
External: the relay output is controlled remotely 
either through software or by a PLC using 
commands sent through communications.
Alarm: the relay output is associated with the 
alarm system. The meter sends a pulse to the 
relay output port when the alarm is triggered.
Behavior Mode
Normal, Timed, Coil Hold
Normal: this applies when control mode is set to 
External or Alarm. The relay output remains in 
the ON state until an OFF command is sent by 
the computer or PLC.
Timed: the relay output remains ON for the period 
defined by the On Time setup register.
Coil Hold: this applies when control mode is set to 
External or Alarm. For a unary alarm that is 
associated with a relay output, you must set 
Behavior Mode to Coil Hold. The output turns on 
when the “energize” command is received and 
turns off when the “coil hold release” command is 
received. In the event of a control power loss, the 
output remembers and returns to the state it was 
in when control power was lost.