Chapter 10—Multi-tariff feature
PowerLogic™  PM5300 series user guide
All days have a tariff applied between 23:00 and 04:59, corresponding to off-peak 
hours. All weekend days have a tariff applied from 05:00 to 22:59, corresponding to 
shoulder hours. All weekdays fall into one of two seasons (summer or winter), and have 
two tariffs applied throughout the day. Example dates and corresponding tariffs:
Wednesday, March 21, 08:00 = tariff 3
Tuesday, January 10, 21:00 = tariff 3
Sunday, June 24, 14:00 = tariff 4
Friday, August 17, 00:00 = tariff 1
Input mode overview
You can use this mode to have the device’s digital inputs set which tariff is applied to 
the energy that is presently being consumed. If a digital input is used for multi-tariff, it 
cannot be used for an exclusive association (such as Demand Sync or Input Metering), 
but digital inputs can be shared with a non-exclusive association (such as Alarms). To 
make a digital input available for setting tariffs, any conflicting associations must be 
manually removed at the source of the original association.
The number of different tariffs that can be applied is determined by the number of 
available digital inputs and the total number of tariffs supported by your device. The 
digital inputs are used as binary counters to identify the appropriate tariff, where off = 0 
and on = 1, and most significant bit (MSB) is digital input 2 and least significant bit 
(LSB) is digital input 1. By this definition, digital input 1 must be associated with the 
multi-tariff feature in order to set the tariff to Input mode.
Configuration 2: one season for weekends, with off-peak and shoulder hours, 
two seasons for weekdays, with shoulder hours
Tariff
Type
Start date
End date
Start time
End time
1
Every day
January 1
December 31
23:00
04:59
2
Weekdays
May 1
September 30
05:00
22:59
3
Weekdays
October 1
April 30
05:00
22:59
4
Weekends
January 1
December 31
05:00
22:59
Digital input requirements for required number of tariffs
Number of 
tariffs required
Digital inputs required
Configuration 1
Configuration 2
1
1 (digital input 1)
1 (digital input 1)
2
1 (digital input 1)
2 (digital input 1 and 2)
3
2 (digital input 1 and 2)
2 (digital input 1 and 2)
4
2 (digital input 1 and 2)
2 (digital input 1 and 2)
Configuration 1: 2 tariff assignment using 2 digital inputs
1
1
There is no inactive tariff with this configuration.
Tariff
Digital input 2
Digital input 1
T1
0
0
T2
0
1
Configuration 2: 2 tariff assignment using 2 digital inputs
Tariff
Digital input 2
Digital input 1
None
1
1
This digital input configuration (00) means there are no active 
tariffs (all tariffs are disabled)
0
0
T1
0
1
T2
1
0