Schneider Electric PM5300 Manual De Usuario

Descargar
Página de 120
88
© 2014 Schneider Electric All Rights Reserved
Chapter 10—Multi-tariff feature
PowerLogic™  PM5300 series user guide
7. Modify each parameter as required, then press OK to set. Press   or   to move 
between parameters.
8. Press   to exit, then Yes to save your changes. Repeat for the other tariffs as 
required. The meter checks the configuration and display a message if any tariffs 
have conflicting settings (i.e., overlapping tariff periods).
Configuring input mode tariffs using the front panel
When you set the tariff type to Input, the active tariff is determined by the status of the 
digital inputs.
Digital inputs are available for tariffs if they are not used, or if they are only associated 
with alarms (Normal). To make a digital input available, you must manually disconnect 
the conflicting association before configuring tariffs.
You cannot configure any digital input tariff if digital input 1 is not available for 
association. Likewise, digital input 2 must be available to select more than two tariffs. 
The status of the digital inputs is used to calculate the binary value of the active tariff, 
where off = 0 and on = 1. The calculation of the number of tariffs value can differ, 
depending on the number of digital inputs that can be selected (i.e., inputs that can be 
associated with multi-tariff).
To configure input mode tariffs using the front panel:
1. Navigate to Maint > Setup.
2. Enter the setup password (default is “0”), then press OK.
3. Navigate to Meter > Tariff.
4. With the cursor pointing to Mode, press Edit.
5. Press   or   to change the setting to Input, then press OK.
NOTE:
If a digital input association error prompt displays, you must exit from the tariff 
setup screens and remove the digital input association.
6. Navigate to Tariffs, then press Edit.
7. Press   or   to change the number of tariffs you want to set up. The maximum 
number of tariffs that you can apply is determined by the number of available digital 
inputs, as described in the table, “Digital input requirements for required number of 
tariffs” on page 86
. Press OK.
8. Navigate to Inputs, then press Edit.
9. If applicable, press   or   to change how many digital inputs you want to use to 
control which tariff is selected (active). Press OK.
10. Press 
 to exit, then Yes to save your changes.
Start Month
1 to 12
Set the month that the tariff period starts, 
where 1 = January, 2 = February, 3 = March, 
4 = April,  5 = May,  6 = June,  7 = July, 
8 = August, 9 = September, 10 = October, 
11 = November, 12 = December.
Start Day
1 to 31
Set the day of the Start Month that the tariff 
period starts. The Start Day must be earlier 
than End Day if Start Month equals End 
Month.
End Month
1 to 12
The month that the tariff period ends, where 
1 = January, 2 = February, 3 = March, 
4 = April,  5 = May,  6 = June,  7 = July, 
8 = August, 9 = September, 10 = October, 
11 = November, 12 = December.
End Day
1 to 31
The day of the End Month that the tariff 
period ends. 
Time of day mode tariff setup (continued)
Parameter
Values
Description