Table 5 - RJ45 Ethernet port pin-out 
 
NOTE: RuggedCom does not recommend the use of CAT-5 (10/100Base-TX communications) 
cabling of any length for critical real-time substation automation applications. However, transient 
suppression circuitry is present on all copper ports to protect against damage from electrical 
transients and to ensure IEC 61850-3 and IEEE 1613 Class 1 conformance. This means that 
during the transient event communications errors or interruptions may occur but recovery is 
automatic.  
 
RuggedCom also does not recommended to use these ports to interface to field devices across 
distances which could produce high levels of ground potential rise, (i.e. greater than 2500V) during 
line to ground fault conditions.  
 
4.3  Fiber Optic Ethernet Ports 
 
Depending on the order code of the product, the RS910L can be equipped with several different 
fiber optic ports. The Transmit (Tx) and Receive (Rx) connections of each port must be properly 
connected and matched for proper link and operation.  The drawings in the following figures show 
each fiber optical connector style with a side and top view to allow the user to identify the proper 
cable connection orientation.   
 
 
 
Figure 15:  10FL ST connector 
 
 
Figure 16:  100FX MTRJ connector 
 
 
 
Figure 17:  100FX ST connector