RuggedCom RS910L Manual De Usuario

Descargar
Página de 29
23 
 
2007 RuggedCom Inc. All rights reserved 
 
Rev100
 
5  Technical Specifications 
 
5.1  Operating Environment 
 
Parameter 
Range 
Comments 
Ambient Operating Temperature 
-40 to 85
°C 
Ambient Temperature as 
measured from a 30 cm radius 
surrounding the center of the 
RS910 enclosure. 
Ambient Storage Temperature 
-40 to 85
°C 
 
Ambient Relative Humidity 
5% to 95% 
Non-condensing 
Table 6 - Operating Environment 
 
5.2  Power Supply Specifications 
 
Power Supply Type 
Minimum 
Input 
Maximum 
Input 
Fuse 
Rating 
Isolation 
Maximum Power 
Consumption 
12 – 24 VDC 
10 VDC 
36 VDC 
3.15 (T) 
1.5 kV DC 
24 VDC 
18 VDC 
36 VDC 
3.15 (T) 
1.5 kV DC 
48 VDC 
36 VDC 
72 VDC 
3.15 (T) 
1.5 kV DC 
HI (125/250 VDC) 1 
HI (110/230 VAC) 1 
88 VDC 
85 VAC 
300 VDC 
265 VAC 
3.15 (T) 
4 kV AC  5.5 
kV DC 
10W 
Table 7 - Power Supply Specifications 
 
NOTES:   
1.
  This is the same power supply for both AC and DC. 
2.
  (F) Denotes fast-acting fuse, (T) denotes time-delay fuse. 
3.
  For continued protection against risk of fire, replace only with same type and rating of fuse. 
 
5.3  Failsafe Relay Specifications 
 
 
Load Circuit 
SELV 
TNV-2 
MAX operating Voltage 
30VDC 
30 VAC 
80VDC 
MAX operating Current 
1A 
0.5A 
0.3A 
Isolation (between coil and contacts) 
1800 V
rms
 
Table 8 - Failsafe Relay Specifications