Smart-UPS X-Series Operation
10
Network Management Card Settings 
These settings are available only on units that have a Network Management Card (NMC) and are set in 
the factory. These settings can only be modified using an external interface, like the NMC web interface.
•   NMC  IP  Address  Mode
•   NMC  IP  Address
•  NMC Subnet Mask
•  NMC Default Gateway
Load Shed Time 
when On Battery
Disabled
0-32767 sec
The amount of time the outlets will function on 
battery power before they will turn off.
Load Shed On 
Runtime
Disabled
• Shutdown with 
delay
• Shutdown 
immediately
• Turn off 
immediately
• Turn off with 
delay
• Disabled
When the battery runtime falls below the 
specified value, the Controllable Outlet Group 
will turn off.
Configure this time using the 
L
OAD
 S
HED
 
R
UNTIME
 R
EMAINING
 setting.
Load Shed On 
Runtime 
Remaining
Disabled
0-32767 sec
When the remaining runtime reaches this level, 
the Controllable Outlet Group will turn off.
Load Shed on 
Overload
Disabled
• Disabled
• Enabled
(Applicable only for Controllable Outlet 
Groups, not the UPS outlets.) When enabled, 
the Controllable Outlet Group will turn off 
immediately in the event of a power outage 
and will have to be manually restarted.
Function
Factory Default Options
Description