3.2 OPERATION 
MODES 
 
This section describes the different possible operation modes of the UPS explaining the function of the 
main modules of the UPS. 
 
 
VFI (Voltage Frequency Independent) Mode operation 
 
Under normal conditions the load is 
permanently powered by the inverter with 
constant amplitude and frequency. 
 
The rectifier, powered by the mains, supplies the 
inverter and the battery-charger keeps the 
battery fully charged. 
 
Fig. 3.2-1   Energy flow in VFI Mode operation 
 
The  inverter converts the DC voltage in a new AC sine wave voltage with constant amplitude and 
frequency independently from the input mains power
 
 
 
ECO Mode operation (Intelligent Energy Management) 
 
When the ECO Mode is selected, and the mains 
power is available, the load is normally powered 
through the automatic bypass
 
When the mains voltage is detected out of the 
prescribed tolerances, the load is automatically 
transferred to the inverter
 
When the mains recovers, the load returns to 
the  automatic bypass after a variable time 
defined by the control unit. 
 
Fig. 3.2-2   Energy flow in ECO Mode operation 
 
The ECO Mode can be configured directly by the user for higher efficiency, considering the mains 
reliability and criticality of the load
 
The selection between the two operation modes “VFI Mode and ECO Mode”, or switching between 
operation modes at required time, can be done through the UPS control panel (see Section 6.3.1-5). 
 
 
     In case of parallel system 
 
ECO Mode cannot be enabled for RPA Parallel System. 
Attention:
 
A single unit equipped with a RPA - Parallel board, must be considered as parallel, thus 
disabling ECO Mode.