Operating Manual LP 33 Series 30 & 40 kVA 
6.2  EVENT SCREENS (Alarm) 
 
Each of the following listed alarms or messages can be displayed on the LCD screen or transmitted to a 
PC through the serial port RS232 or the SNMP card (optional). 
 
Entering the Alarm mode, the LCD screen displays a sequence of screens corresponding to the last 256 
alarms & events, each screen indicating: 
 
01.01.2005 12:15:45 
NR=255 Status=A588 
4580: INVERTER AND 
MAINS SYNCHRONIZED
 
 
1.  The exact date and time when the event occurred. 
2.  The number (255 being the most recent) and status code. 
3.  The software version implemented on control board and 
explicit text description of the event. 
 
 
 
6.2.1 Alarms 
list 
 
Are defined alarms
all the events which activate the LED Warning (yellow) and the buzzer in order 
to alert the user about an abnormal situation. 
 
Code 
Alarm 
Meaning 
 
4000 
SETUP VALUES 
LOST 
Parameters are lost and have been replaced with default 
values. 
4001 
REGULATION BOARD 
FAILURE 
Voltage supply +/-15 VDC has been detected out of tolerance 
on the P1 – Control board or the programmable circuits are 
defective. 
4004 
UPS 
FAILURE 
The master unit detected the slave unit missing on the 
communication bus even though switch Q1 is still closed. 
4100 
RECTIFIER FUSES 
FAILURE 
The trip indicator mounted on rectifier input fuses indicates a 
blown fuse. 
The rectifier is turned Off (K4 open) and the load will be supplied 
by the battery. 
4102 
K4 CLOSING 
FAILURE 
K4 not closed despite a closing command being done. 
The rectifier is switched OFF. 
4103 
K4 OPENING 
FAILURE 
K4 not open despite an opening command being done. 
The rectifier is switched OFF. 
4110 
RECTIFIER MAINS 
OUT OF TOLERANCE 
Rectifier input mains has been detected out of tolerance 
(voltage, frequency or phase). 
4115 
LOW BATTERY 
VOLTAGE 
The battery has been discharged and reached “stop operation” 
time-out (default 3 minutes), the inverter will be shut down. 
It restarts automatically only when the battery has recovered 
energy to ensure min. a “stop operation” time to the actual 
load. 
4116 
HIGH BATTERY 
VOLTAGE 
Dangerous high UDC-Voltage. 
Causes Inverter shutdown. Inverter restarts automatically after 
return to normal floating voltage.