GE LP 33 Manual De Usuario

Descargar
Página de 57
Modifications reserved 
Page 21/57 
OPM_LPS_3UO_30K_40K_0US_V010.doc 
Operating Manual LP 33 Series 30 & 40 kVA 
6 LCD 
SCREEN 
 
 
Shows the UPS system data, events messages and UPS setting. 
The data is displayed on 4 rows, 20 characters each, allowing the operator to select between 7 
languages: English, German, French, Spanish, Italian, Finnish and Polish
If there is no keypad activity during 1 minute the LCD screen will return to default screen. 
 
 
 
6.1  METERING SCREENS (Metering) 
 
This menu allows, when the keypad Metering is pressed, to show on the LCD panel a series of screens 
containing metering information about AC and DC parameters. 
 
LP 33         40kVA  P1 
APPLICATION ON UPS
 
= 70% 
SERVICE REQUIRED
 
 
 
 
1.  UPS family, nominal rating and for RPA: P + No. UPS. 
2.  Load status: application on UPS, on utility, supply off, manual 
bypass (appl. on manual dev.) and ECO Mode
3.  The load amount as a percentage of the nominal load (referred 
to the most loaded phase). 
4.  The signalling, combined with the green LED Operation blinking, is done only in case the respective 
parameter (protected by password) has been enabled. See Section 8.4
 
 
 
Udcp=215V Udcn=215V 
Ubp=164V Ubn=164V  O 
Charge Level 
=  100% 
Autonomy = 
15min
 
 
 
 
1.  Booster DC voltage + pole (Udcp) and – pole (Udcn). 
2.  Battery DC voltage + pole (Ubp), – pole (Ubn) and the status 
SBM (Superior Battery Management). 
The functionality of SBM can help to reduce the Battery 
recharging time, and improve the lifetime of the Battery. 
 
Beside the indication of the Battery voltage on the display, a letter shows, according to the table 
below, the operational status of SBM
 
Sigle 
Status of charger 
Charter voltage 
Description 
OFF 
0 VDC 
Battery open circuit voltage 
ON 
Boost (176 VDC) 
Boost charge with new Battery 
ON 
Floating (164 VDC) 
Battery charged 
ON 
Floating (164 VDC) 
Normal charge 
ON 
Boost (176 VDC) 
Boost charge 
ON 
Boost (179 VDC) 
Battery equalization 
Access to the Parameters for setting the SBM mode is password protected. 
Please call your Service Center
3. Battery 
charge 
level. 
4.  Estimated battery backup time with actual load.