Operating Manual LP 33 Series 30 & 40 kVA 
6.2.2 Messages 
list 
 
Are defined messages:  
all the recorded events which are referred to the operation status coherent 
with the normal situation of the UPS. 
 
Code 
Message 
Meaning 
 
4111 
RECTIFIER 
MAINS OK 
Rectifier input mains is again within the admitted tolerance 
(voltage, frequency and phase). 
4114 
UPS SHUTDOWN 
(LOW BATT VOLTAGE) 
The UPS is in Load OFF status, resulting in Battery supply for the 
power supply. 
Should the Battery voltage decrease to a value below of the one 
set in a parameter, then power supply will shutdown to avoid 
damage to the Battery 
4119 
BATTERY TEST 
STARTED 
Start of manual or automatic battery test. 
Rectifier output voltage is decreased to the value defined by 
respective parameter. 
4120 
BATTERY TEST 
STOPPED 
End battery test. 
End of manual or automatic battery test. 
Rectifier output voltage is restored to floating voltage. 
4141 
ISMAX DETECTION 
BOOSTER 
Detection of persistent booster (Is) current limitation. 
4161 
RECTIFIER 
ON 
Rectifier received the command to switch ON. 
4162 
RECTIFIER 
OFF 
Rectifier received the command to switch OFF for: 
input mains out of tolerance / EPO / UDC max. 
4163 
GENERATOR 
ON 
Customer Interface (X1 / 11, 22) received a Gen set ON signaling. 
Operating mode dependent on setting of respective parameters. 
4164 
GENERATOR 
OFF 
Customer Interface (X1 / 11, 22) received a Gen set OFF 
signaling. 
Function bypass enabled dependent on setting of respective 
parameter. 
4302 
INVERTER 
CANNOT BE 
TURNED ON 
Inverter cannot be switched on because one of the following 
conditions are still present: 
•  Overtemperature; 
•  Low battery voltage; 
•  Inverter fuses; 
•  Overload; 
•  K7 opening failure; 
•  High battery voltage; 
•  DC low; 
•  EPO (Emergency Power Off). 
4303 
INVERTER 
CANNOT BE 
TURNED OFF 
Inverter cannot be switched OFF, because the load cannot be 
transferred on mains (voltage out of tolerance, not 
synchronizing, bypass blocked). 
4361 
INVERTER 
ON 
The command to start the inverter has been activated on the 
control panel.