Operating Manual LP 33 Series 30 & 40 kVA 
Code 
Message 
Meaning 
 
4362 
INVERTER 
OFF 
The command to switch OFF the inverter has been done by the 
control panel or automatically for alarm detection. 
4411 
BYPASS MAINS 
OK 
Bypass input mains is again within the admitted tolerance 
(voltage, frequency and phase). 
4500 
COMMAND 
LOAD OFF 
Disconnection of the load by opening K4, K6 and K7 for: 
EPO / Total Off / Overload / Stop operation. 
4521 
NO BYPASS 
POWER 
With the load supplied by electronic bypass, a mains failure or 
K6 opening occurred. 
4534 
MULTIPLE LOAD 
TRANSFER 
2 transfers inverter-mains have been detected in a short time, 
defined by respective parameter (default 30 seconds). 
4535 
BYPASS 
LOCKED 
Transfer on mains not enabled due to settings of respective 
parameters. Contactor K6 is open. 
4536 
BYPASS 
FREE 
Settings of respective parameters enable bypass transfer on 
mains. 
Contactor K6 can be closed. 
4561 
TOTAL 
OFF 
Push-button Total Off behind the front door has been pressed, 
with the output circuit breaker Q1 closed. 
4562 
DETOUR 
ON 
The auxiliary contact indicates that manual bypass Q2 has 
been closed. 
4564 
DETOUR 
OFF 
The auxiliary contact indicates that manual bypass Q2 has 
been opened. 
4567 
COMMAND 
LOAD ON MAINS 
The control unit received a command to transfer the load on 
mains. 
4568 
COMMAND 
LOAD ON INVERTER 
The control unit received a command to transfer the load on 
inverter. 
4572 
NO MORE 
OVERLOAD 
End of the overload condition previously detected with alarm 
4570. 
4580 
INVERTER AND 
MAINS SYNCHRONIZED 
The voltages of inverter and mains bypass are synchronized. 
4582 
COMMAND NOT TO 
SYNCHRONIZE 
Command not to synchronize with mains has been done for: 
mains bypass out of tolerance (4410) or setting respective 
parameters. 
4583 
COMMAND TO 
SYNCHRONIZE 
Command to synchronize with mains has been done for: 
mains BP OK (4410) or setting respective parameters. 
4600 
COMMAND 
UPS ON 
The ECO Mode function has been disabled or the programmed 
time is expired. 
The UPS returns to VFI Mode supplying the load normally by 
inverter. 
4601 
COMMAND UPS 
STAND BY 
The function ECO Mode is enabled, and according to the time 
program the UPS will run in ECO Mode, supplying the load 
normally by mains.